HP Indigo 10000 B&R Drivers Troubleshooting -- Document P/N:CA493-00610 Re - Page 15

Check POWERLINK Ethernet connections., RDY LED is lit green. If the LED is OFF

Page 15 highlights

b. If the LED is still blinking (no enable signals) and the interlocks are closed, check enable input voltage (connector X1 pin couples 1, 2 and 3, 4). 6. If the RDY indication LED is not lit green, do the following: a. If the LED is blinking (no enable signals), check interlocks and make sure the press is not in OFF status. b. If the LED is still blinking (no enable signals) and the interlocks are closed, check enable input voltage (connector X1 pin couples 1, 2 and 3, 4). c. If the LED is still blinking, check the motor encoder connection and functionality: Rotate the motor. Only one of the UP/DN LEDs should be blinking at any given time. d. If the LED is OFF, check the 560 V power supply and verify that the E-stop was not pressed. 7. In the case of a 560 V power supply failure, check that: a. RDY LED is lit green. If the LED is OFF, check 400 V at the power supply input (connector X5A) and verify that the E-stop was not pressed. b. Auxiliary power supply (24 V) RDY LED is lit green. If the LED is OFF and the 560 V power supply is active, replace auxiliary power supply module. 8. If neither the L/D1 nor the L/D2 LED is blinking, do the following: a. Check POWERLINK (Ethernet) connections. Instructions 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61

b.
If the LED is still blinking (no enable signals) and the interlocks are closed, check enable input
voltage (connector X1 pin couples 1, 2 and 3, 4).
6.
If the RDY indication LED is not lit green, do the following:
a.
If the LED is blinking (no enable signals), check interlocks and make sure the press is not in OFF
status.
b.
If the LED is still blinking (no enable signals) and the interlocks are closed, check enable input
voltage (connector X1 pin couples 1, 2 and 3, 4).
c.
If the LED is still blinking, check the motor encoder connection and functionality: Rotate the
motor. Only one of the UP/DN LEDs should be blinking at any given time.
d.
If the LED is OFF, check the 560 V power supply and verify that the E-stop was not pressed.
7.
In the case of a 560 V power supply failure, check that:
a.
RDY LED is lit green. If the LED is OFF, check 400 V at the power supply input (connector X5A)
and verify that the E-stop was not pressed.
b.
Auxiliary power supply (24 V) RDY LED is lit green. If the LED is OFF and the 560 V power supply
is active, replace auxiliary power supply module.
8.
If neither the L/D1 nor the L/D2 LED is blinking, do the following:
a.
Check POWERLINK (Ethernet) connections.
Instructions
13