HP Latex 3200 Site Preparation Guide - Page 11

Power distribution unit PDU, Power specifications

Page 11 highlights

NOTE: Remember that you are required to follow the local laws, regulations, and standards that apply to the electrical installation of your printer. NOTE: The printer is not supplied with any power cable. Power distribution unit (PDU) The PDU must be rated to meet the power requirements of the printer, and should be in accordance with the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed. Power specifications NOTE: If you purchased a Jumbo Roll Solution, check electrical specifications. See Additional electrical configuration for the jumbo roll units on page 10. Configuration 1: 380-415 V line-to-line three-phase configuration Three-phase specifications Number of power wires 5 (L1/L2/L3/N/PE) Input voltage (line-to-line) 380-415 V Input frequency 50/60 Hz Power consumption (typical) 9-11 kW Maximum load current (per phase) 35 A Branch circuit breaker specifications Three-phase 4 poles, 40/50 A AC three-phase power cable specifications Configuration 5 wires, L1/L2/L3/N/PE Wire Strained Cu minimum, 10 mm² or 8 AWG Terminals Lines, ferrule terminals, PE, M8 ring terminal External diameter range 22.0-33.0 mm Configuration 2: 200-240 V line-to-line three-phase configuration Three-phase specifications Number of power wires) 4 (L1/L2/L3/PE) Input voltage (line-to-line) 200-240 V Input frequency 50/60 Hz Power consumption (typical) 9-11 kW Maximum load current (per phase) 56 A Branch circuit breaker specifications Three-phase 3 poles, 63/70 A ENWW System operation requirements 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37

NOTE:
Remember that you are required to follow the local laws, regulations, and standards that apply to the
electrical installation of your printer.
NOTE:
The printer is not supplied with any power cable.
Power distribution unit (PDU)
The PDU must be rated to meet the power requirements of the printer, and should be in accordance with the
Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
Power specifications
NOTE:
If you purchased a Jumbo Roll Solution, check electrical specifications. See
Additional electrical
configuration
for the jumbo roll units
on page
10
.
Configuration 1: 380–415 V line-to-line three-phase configuration
Three-phase specifications
Number of power wires
5 (L1/L2/L3/N/PE)
Input voltage (line-to-line)
380–415 V
Input frequency
50/60 Hz
Power consumption (typical)
9–11 kW
Maximum load current (per phase)
35 A
Branch circuit breaker specifications
Three-phase
4 poles, 40/50 A
AC three-phase power cable specifications
Configuration
5 wires, L1/L2/L3/N/PE
Wire
Strained Cu minimum, 10 mm² or 8 AWG
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
External diameter range
22.0–33.0 mm
Configuration 2: 200–240 V line-to-line three-phase configuration
Three-phase specifications
Number of power wires)
4 (L1/L2/L3/PE)
Input voltage (line-to-line)
200–240 V
Input frequency
50/60 Hz
Power consumption (typical)
9–11 kW
Maximum load current (per phase)
56 A
Branch circuit breaker specifications
Three-phase
3 poles, 63/70 A
ENWW
System operation requirements
7