HP Latex 3200 Site Preparation Guide - Page 14
may be needed.
View all HP Latex 3200 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 14 highlights
Specifications (continued) Input voltage (line-to-line) Input frequency Power consumption (typical) Maximum load current (per phase) Two-phase line 240 V 50/60 Hz 9-11 kW 72 A Single-phase control 100-240 V 50/60 Hz 0.5 kW 10 A Branch circuit breaker specifications Two-phase line Two-phase control 2 poles, 90 A 2 poles, 15/16/20 A AC power cable specifications Configuration Wire Terminals External diameter range Two-phase line Single-phase control 3 wires, L1/L2/ PE 3 wires, L/N/PE Strained Cu minimum, 4 AWG Strained Cu minimum, 1.5 mm² or 16 AWG Lines, ferrule terminals, PE, M8 ring terminal Lines, ferrule terminals, PE, M4 ring terminal 22.0-33.0 mm 5.0-11.0 mm If your facilities do not provide the required AC 400VAC line-to-line voltage additional transformer equipment may be needed. Additional electrical configuration for the jumbo roll units Each jumbo unit requires an independent power line, complaint with the following specifications: Three-phase specifications: Number of power wires Input voltage (line-to-line) Input frequency Power consumption (typical) Maximum load current (per phase) Jumbo unit 4 (L1/L2/L3/PE) 400 V 50/60 Hz 2.5 kW 6 A Branch circuit breaker specifications Three-phase 3 poles, 10 A per unit AC three-phase power cable specifications Configuration Jumbo input/output units 4 (L1/L2/L3/PE) 10 Chapter 2 Site preparation ENWW