Lantronix XPort APS: Modbus Protocol User Guide - Page 27
Micro125 Implementation
View all Lantronix XPort manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 27 highlights
8: Micro125 Implementation The Modbus master/slave functionality on the Micro125 is similar to the Modbus implementation on other platforms such as the xPico-IAP and xDirect-IAP. The Micro125 product does not support configurable pins, so they are not applicable in the Setup Menu. The Micro125 has 1 serial port. In this serial port, hence the firmware uses for sending and receiving Modbus/RTU or Modbus/ASCII serial data under the Serial & Mode Settings menu option. The setting for each configuration option is displayed in the setup menu. Modbus/TCP to RTU Bridge Setup 1) Network/IP Settings: IP Address 0.0.0.0/DHCP/BOOTP/AutoIP Default Gateway not set --Netmask not set --2) Serial & Mode Settings: Protocol Modbus/RTU,Slave(s) attached Serial Interface 9600,8,N,1,RS232,CH1 3) Modem/Configurable Pin Settings: RTS Output Fixed High/Active 4) Advanced Modbus Protocol settings: Slave Addr/Unit Id Source .. Modbus/TCP header Modbus Serial Broadcasts ... Disabled (Id=0 auto-mapped to 1) MB/TCP Exception Codes ..... Yes (return 00AH and 00BH) Char, Message Timeout ...... 00050msec, 05000msec 7) Security Settings: SNMP Enabled SNMP Community Name ........ public Telnet Setup Enabled TFTP Download Enabled Port 77FEh Enabled Web Server Enabled Enhanced Password .......... Disabled D)efault settings, S)ave, Q)uit without save Select Command or parameter set (1..7) to change: Modbus Protocol User Guide 27