Sanyo 24KHS72 Service Manual - Page 18
Refrigerant Flow Diagram - split a c heat
View all Sanyo 24KHS72 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 18 highlights
4. REFRIGERANT FLOW DIAGRAM 4-1. Refrigerant Flow Diagram Indoor Unit KHS1872 KHS2472 Outdoor Unit CH1872 CH2472 Indoor unit Wide tube Wide tube service valve *1 Muffler Outdoor unit Accumulator High pressure switch H.P. 4-way valve Compressor Heat exchanger Heat exchanger Narrow tube Narrow tube service valve Capillary tube for Electric split flow expansion valve M O.D. 1/4" (6.35 mm) Strainer *1 O.D.1/2"(12.7 mm) ......... 1872 class O.D.5/8"(15.88 mm) ......... 2472 class Cooling cycle (Defrosting cycle) Heating cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation Thickness: Min. 5/16"(8 mm) should be a min. 5/16"(8 mm). CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. Wide tube Insulation Thickness: Min. 5/16"(8 mm) Narrow tube 18