Cisco ASR1006-10G-SEC/K9 Installation Guide - Page 29

When you install the unit, the ground connection must always be made first and disconnected last.

Page 29 highlights

Chapter 6 Cisco ASR 1006 Router Overview and Installation Connecting Power to the Cisco ASR 1006 Router Each DC input power cable is terminated at the PDU by a cable lug. The cable lugs must be dual-hole, and have a straight tongue. They must be able to fit over 1/4-inch terminal studs at 0.625-inch (15.88-mm) centers. Note DC input power cables must be connected to the PDU terminal studs in the proper positive (+) and negative (-) polarity. In some cases, the DC cable leads are labeled, which is a relatively safe indication of the polarity. However, you must verify the polarity by measuring the voltage between the DC cable leads. When making the measurement, the positive (+) lead and the negative (-) lead must always match the (+) and (-) labels on the power distribution unit. • A ground cable is required for each DC PDU. We recommend that you use at least 6-AWG multistrand copper wire. This wire is not available from Cisco Systems; it is available from any commercial cable vendor. The ground wire cable lug should be dual-hole (see Figure 6-20) and able to fit over M6 terminal studs at 0.625 inch (15.88mm) centers. Recommended lug terminal wire size Panduit part number: - LCD8-14A-L for 8AWG wire size - LCD6-14A-L for 6AWG wire size Figure 6-20 DC Input Power Cable Lug 2.24 End View All measurements in inches 0.48 Ø 0.267 2 holes 0.25 0.63 0.37 0.08 Crimp area 25527 Note To avoid hazardous conditions, all components in the area where DC input power is accessible must be properly insulated. Therefore, before installing the DC cable lugs, be sure to insulate the lugs according to the manufacturer's instructions. Warning When you install the unit, the ground connection must always be made first and disconnected last. Statement 1046 To connect the DC power supply, follow these steps: Step 1 Step 2 Make certain that the chassis grounding is connected before you begin installing the DC power supply. Locate the stud on the DC power supply for the GND connection which must be connected first and follow these steps: a. Using the grounding lug, replace the washers and Kepnut screw in the following order. - Flat washer OL-13208-09 Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation Guide 6-29

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

6-29
Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation Guide
OL-13208-09
Chapter 6
Cisco ASR 1006 Router Overview and Installation
Connecting Power to the Cisco ASR 1006 Router
Each DC input power cable is terminated at the PDU by a cable lug. The cable lugs must be
dual-hole, and have a straight tongue. They must be able to fit over 1/4-inch terminal studs at
0.625-inch (15.88-mm) centers.
Note
DC input power cables must be connected to the PDU terminal studs in the proper positive
(+) and negative (–) polarity. In some cases, the DC cable leads are labeled, which is a
relatively safe indication of the polarity. However, you must verify the polarity by measuring
the voltage between the DC cable leads. When making the measurement, the positive (+)
lead and the negative (–) lead must always match the (+) and (–) labels on the power
distribution unit.
A ground cable is required for each DC PDU. We recommend that you use at least 6-AWG
multistrand copper wire. This wire is not available from Cisco Systems; it is available from any
commercial cable vendor.
The ground wire cable lug should be dual-hole (see
Figure 6-20
) and able to fit over M6 terminal
studs at 0.625 inch (15.88mm) centers. Recommended lug terminal wire size Panduit part number:
LCD8-14A-L for 8AWG wire size
LCD6-14A-L for 6AWG wire size
Figure 6-20
DC Input Power Cable Lug
Note
To avoid hazardous conditions, all components in the area where DC input power is
accessible must be properly insulated. Therefore, before installing the DC cable lugs, be sure
to insulate the lugs according to the manufacturer’s instructions.
Warning
When you install the unit, the ground connection must always be made first and disconnected last.
Statement 1046
To connect the DC power supply, follow these steps:
Step 1
Make certain that the chassis grounding is connected before you begin installing the DC power supply.
Step 2
Locate the stud on the DC power supply for the
GND
connection which must be connected first and
follow these steps:
a.
Using the grounding lug, replace the washers and Kepnut screw in the following order.
Flat washer
Crimp area
25527
2.24
0.48
0.08
0.25
0.37
0.63
End View
Ø 0.267
2 holes
All measurements in inches