Dell PowerEdge T320 Owner's Manual - Page 144
Expanded Operating Temperature Restrictions, cooling fan must be installed.
View all Dell PowerEdge T320 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 144 highlights
Environmental Expanded Operating Temperature Restrictions NOTE: Outside the standard operating temperature of 10 °C to 35 °C (50 °F to 95 °F), the system can operate down to -5 °C or up to 45 °C for a maximum of 1% of its annual operating hours. For temperatures between 40 °C and 45 °C (104 °F to 113 °F), de-rate maximum allowable dry bulb temperature by 1 °C per 125 m above 950 m (1 °F per 228 ft). • Both the internal cooling fan and the external cooling fan must be installed. • The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft). • GPU is not supported. • Non-redundant power supplies are not supported. • Non Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported. 144
Environmental
NOTE:
Outside the standard operating temperature of
10 °C to 35 °C (50 °F to 95 °F), the system can operate
down to –5 °C or up to 45 °C for a maximum of 1% of
its annual operating hours.
For temperatures between 40 °C and 45 °C (104 °F to 113
°F), de-rate maximum allowable dry bulb temperature by
1 °C per 125 m above 950 m (1 °F per 228 ft).
Expanded Operating Temperature Restrictions
•
Both the internal cooling fan and the external
cooling fan must be installed.
•
The operating temperature specified is for a
maximum altitude of 3050 m (10,000 ft).
•
GPU is not supported.
•
Non-redundant power supplies are not
supported.
•
Non Dell qualified peripheral cards and/or
peripheral cards greater than 25 W are not
supported.
144