HP 6400/8400 HP StorageWorks 6400/8400 Enterprise Virtual Array User Guide - Page 109
Shock and vibration specifications, Table 26 EVA8400 UPS loading, Table 28 Operating Shock/Vibration
View all HP 6400/8400 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 109 highlights
Table 26 EVA8400 UPS loading Enclosures Watts 12 4920 11 4414 10 4037 9 3660 8 3284 7 2907 6 2530 5 2153 4 1777 3 1400 2 1023 1 647 Table 27 EVA6400 UPS loading Enclosures 8 7 6 5 4 3 2 1 Watts 3214 2837 2460 2083 1707 1330 953 577 R3000 91.1 77.2 63.2 49.3 35.3 21.4 % of UPS capacity R5500 R12000 41.0 98.1 36.8 89.7 33.6 81.3 30.5 73.0 27.4 64.6 24.2 56.2 21.1 47.9 17.9 39.5 14.8 31.1 11.7 22.7 8.5 14.4 5.4 % of UPS capacity R5500 71.4 63.0 54.6 46.2 37.9 29.5 21.2 12.8 R12000 26.8 23.6 20.5 17.3 14.2 11.1 7.9 4.8 Shock and vibration specifications Table 28 (page 109) lists the product operating shock and vibration specifications. This information applies to products weighing 45 Kg (100 lbs) or less. NOTE: HP P6000 EVA products are designed and tested to withstand the operational shock and vibration limits specified in Table 28 (page 109). Transmission of site vibrations through non-HP racks exceeding these limits could cause operational failures of the system components. Table 28 Operating Shock/Vibration Shock test with half sine pulses of 10 G magnitude and 10 ms duration applied in all three axes (both positive and negative directions). Sine sweep vibration from 5 Hz to 500 Hz to 5 Hz at 0.1 G peak, with 0.020" displacement limitation below 10 Hz. Sweep rate of 1 octave/minute. Test performed in all three axes. Environmental and operating specifications 109