HP BL10e HP ProLiant BL e-Class System Maintenance and Service Guide - Page 33

Fan Cage, Remove all server blades. See the Removing a Server Blade in

Page 33 highlights

Removal and Replacement Procedures • Hard drive • Server blade battery • Center wall assembly Fan Cage To remove the fan cage: 1. Power down each server blade. See the "Powering Down a Server Blade" section in this chapter. 2. Power down the enclosure. See the "Powering Down the Enclosure" section in this chapter. 3. Disconnect all cables and power cords from the AC power source. 4. Disconnect all cables and power cords from the enclosure rear panel. 5. Remove all server blades. See the "Removing a Server Blade" section in this chapter. CAUTION: Integrated Administrator security settings are assigned to server blade bays, not to server blades. If server blades change locations within the enclosure, Integrated Administrator settings must also be adjusted to ensure accurate security. Refer to the HP ProLiant BL e-Class Integrated Administrator User Guide for more information on security settings. 6. Remove both hot-plug power supplies. See the "Hot-Plug Power Supplies" section in this chapter. 7. Remove the interconnect tray. See the "Removing the Interconnect Tray" section in this chapter. 8. Remove the enclosure from the rack. See the "Removing the Server Blade Enclosure from the Rack" section in this chapter. 9. Place the enclosure on a level, nonconductive surface. 2-18 HP ProLiant BL e-Class System Maintenance and Service Guide HP CONFIDENTIAL Codename: MacDuff Part Number: 249066-005 Last Saved On: 7/11/03 7:27 AM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84

Removal and Replacement Procedures
Hard drive
Server blade battery
Center wall assembly
Fan Cage
To remove the fan cage:
1.
Power down each server blade. See the “Powering Down a Server Blade” section in this
chapter.
2.
Power down the enclosure. See the “Powering Down the Enclosure” section in this
chapter.
3.
Disconnect all cables and power cords from the AC power source.
4.
Disconnect all cables and power cords from the enclosure rear panel.
5.
Remove all server blades. See the “Removing a Server Blade” section in this chapter.
CAUTION:
Integrated Administrator security settings are assigned to server blade bays, not
to server blades. If server blades change locations within the enclosure, Integrated
Administrator settings must also be adjusted to ensure accurate security. Refer to the
HP
ProLiant BL e-Class Integrated Administrator User Guide
for more information on security
settings.
6.
Remove both hot-plug power supplies. See the “Hot-Plug Power Supplies” section in this
chapter.
7.
Remove the interconnect tray. See the “Removing the Interconnect Tray” section in this
chapter.
8.
Remove the enclosure from the rack. See the “Removing the Server Blade Enclosure
from the Rack” section in this chapter.
9.
Place the enclosure on a level, nonconductive surface.
2-18
HP ProLiant BL e-Class System Maintenance and Service Guide
HP CONFIDENTIAL
Codename: MacDuff Part Number: 249066-005 Last Saved On: 7/11/03 7:27 AM