Facility Requirements, Table 18: Facility Requirements, To ensure correct operation of the switch
View all HP StorageWorks 2/16V manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 95 highlights
Technical Specifications Facility Requirements To ensure correct operation of the switch, the facility where the switch is in use must meet the following requirements shown in Table 18: Table 18: Facility Requirements Type Electrical Thermal Cabinet (when rack-mounted) Requirements Primary AC Input 100-240 VAC, 1.5A, 47-63 Hz (SAN Switch 2/8V) and 100-240 VAC, 2.0A, 47-63 Hz (SAN Switch 2/16V); switch autosenses input voltage Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on the switch nameplate Circuit protected by a circuit breaker and grounded in accordance with local electrical codes See Table 20 on page 98 for details A minimum air flow of 24 cubic ft/minute available in the immediate vicinity of the switch Ambient air temperature not exceeding 40° C (104° F) while the switch is operating One rack unit in a 19-in. (48.3 cm.) cabinet All equipment in cabinet grounded through a reliable branch circuit connection Additional weight of switch must not exceed the cabinet's weight limits Cabinet must be secured to insure stability in case of unexpected movement, such as an earthquake SAN Switch 2/8V, 2/16V and 2/16N Installation Guide 95