Table 121., Status-Table Fields and Descriptions, Status, StationName, SetStatus
View all Campbell Scientific CR1000KD manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 538 highlights
Appendix B. Status Table and Settings Table 121. Status-Table Fields and Descriptions Fieldname Description Variable Type CalSeOffSet19 Calibration table of singleended offset values. Each integration / range combination has a singleended offset associated with it. These numbers are updated by the background slow sequence if needed in the program. Integer array of 18 CalDiffOffset19 Calibration table of differential offset values. Each integration / range combination has a differential offset associated with it. These numbers are updated by the background slow sequence if needed in the program. Integer array of 18 Default Range close to 0 close to 0 Edit? Info Type Calib Calib 1 The station name written to the header of data files by the datalogger support software (p. 77) is the station name entered when the software was set up to communicate with the CR1000. In contrast, the station name set in the Status table (by typing it directly into the field, using the StationName() instruction, or using the SetStatus() instruction), can be sampled into a data table using data table access syntax. See the Program Access to Data Tables (p. 148) section for more information. 2 PakBus Addresses 1 to 4094 are valid. Addresses >= 4000 are generally reserved for a PC by the datalogger support software (p. 77). 3 Watchdog errors are automatically reset upon compiling a new program. 4 Replace the lithium battery if