HP 14.4kVA HP Monitored Power Distribution Unit User Guide - Page 112
Table 12. PDU and User Alarms and Events Continued, Type Code, Identification and, Index Code
View all HP 14.4kVA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 112 highlights
Maintenance and Alarms Table 12. PDU and User Alarms and Events (Continued) Identification and Type Code Index Code Alarm or Event 2 207400 Temperature Critical High Threshold 2 211000 2 211100 PDU Phase Input Current No Threshold PDU Phase Low Current Warning 2 211200 PDU Phase Low Current Critical 2 211300 PDU Phase Over Current Warning 2 211400 PDU Phase Over Current Critical 2 212000 2 212100 PDU Phase Voltage No Threshold PDU Phase Low Voltage Warning 2 212200 PDU Phase Low Voltage Critical Description The temperature level reading is greater than the value configured as the high temperature critical threshold. No section current threshold has been triggered. The current amperage (A) reading for the specified section is less than the value configured as the low current warning alarm threshold. The current amperage (A) reading for the specified section is less than the value configured as the low current critical alarm threshold. The specified section current amperage (A) reading is greater than the value configured as the over current warning threshold. The specified section current amperage (A) reading is greater than the value configured as the over current critical alarm threshold. No section voltage threshold has been triggered. The specified section voltage reading is less than the value configured as the low voltage warning threshold. The specified section voltage reading is less than the value configured as the low voltage critical threshold. 2 212300 2 212400 2 213000 2 213100 2 221000 2 221100 2 221200 2 221300 2 221400 2 222000 PDU Phase Over Voltage Warning PDU Phase Over Voltage Critical PDU Frequency OK PDU Frequency Out of Range PDU Gang Phase Input Current No Threshold PDU Gang Phase Low Current Warning PDU Gang Phase Low Current Critical PDU Gang Phase Over Current Warning PDU Gang Phase Over Current Critical PDU Gang Phase Voltage No Threshold The specified section voltage reading is greater than the value configured as the over voltage warning threshold. The specified section voltage reading is greater than the value configured as the over voltage critical threshold. Utility frequency is within the +/- 3 Hz of Nominal frequency. Utility frequency greater or less than +/- 3 Hz of Nominal frequency. No section current threshold has been triggered. The current amperage (A) reading for the specified section is less than the value configured as the low current warning alarm threshold. The current amperage (A) reading for the specified section is less than the value configured as the low current critical alarm threshold. The specified section current amperage (A) reading is greater than the value configured as the over current warning threshold. The specified section input current amperage (A) reading is greater than the value configured as the over current critical alarm threshold. No section voltage threshold has been triggered. HP Monitored PDU User's Guide P-164000281-Rev 1 106