HP 14.4kVA HP Monitored Power Distribution Unit User Guide - Page 92

PDU.Input[1].Phase[x].Current

Page 92 highlights

Serial Interface Operation Table 9. PDU CLI Objects (Continued) XML Object Name PDU.Gang[x].Voltage PDU.Input[1].ActivePower PDU.Input[1].ApparentPower PDU.Input[1].ChangedStatus.FrequencyOutOfRange PDU.Input[1].Frequency PDU.Input[1].Mode PDU.Input[1].Phase.Count PDU.Input[1].Phase[x].ActivePower PDU.Input[1].Phase[x].ApparentPower PDU.Input[1].Phase[x].ChangedStatus.OverCurrent PDU.Input[1].Phase[x].ChangedStatus.OverVoltage PDU.Input[1].Phase[x].Current PDU.Input[1].Phase[x].OverCurrent[1].Threshold PDU.Input[1].Phase[x].OverCurrent[3].Threshold PDU.Input[1].Phase[x].OverCurrent[4].Threshold PDU.Input[1].Phase[x].OverVoltage[1].Threshold PDU.Input[1].Phase[x].OverVoltage[2].Threshold PDU.Input[1].Phase[x].OverVoltage[3].Threshold PDU.Input[1].Phase[x].OverVoltage[4].Threshold PDU.Input[1].Phase[x].PeakFactor PDU.Input[1].Phase[x].PercentLoad PDU.Input[1].Phase[x].PhaseID PDU.Input[1].Phase[x].PowerFactor Type Measure Measure Measure Timestamp Measure Constant Constant Measure HideMeasure Timestamp Timestamp Measure Parameter Parameter Parameter Parameter Parameter Parameter Parameter Measure Measure Constant HideMeasure Description Unit Access Voltage Measured on the breaker/section. cV RO For a double pole breaker, it is the Li to Lj voltage. Active Power Measurement. dW RO It is the accumulation of 1 or 3 phase measures. Apparent Power Measurement. dVA RO It is the accumulation of 1 or 3 phase measures. s RO Frequency Measurement. dHz RO Wiring Mode - RO 0: Wye Measuring 1: Delta Measuring 2: Wye Current and Delta Measuring Number of phase managed by the Input module. - RO Active Power Measurement. dW RO Apparent Power Measurement. dVA RO Timestamp of last changing state of the alarm that has the s RO same name in the collection PresentStatus. Timestamp of last changing state of the alarm that has the s RO same name in the collection PresentStatus. Current Measurement. mA RO mA RW mA RW mA RW cV RW cV RW cV RW cV RW Crest factor of the current provided by the phase. m% RO Percent load consumed on the phase. It is the ratio: current % RO consumed / the nominal current of the PDU. Phase ID identifier depending of the wiring: - RO 1: Line 1 to Neutral 2: Line 2 to Neutral 3: Line 3 to Neutral 12: Line 1 to Line 2 23: Line 2 to Line 3 31: Line 3 to Line 1 Ratio of active power / apparent power provided by the phase. m% RO Value 0 to 100 for Cos PHI = 0.00 to 1.00 HP Monitored PDU User's Guide P-164000281-Rev 1 86

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120

Serial Interface Operation
HP Monitored PDU User’s Guide
P-164000281—Rev 1
86
PDU.Gang[x].Voltage
Measure
Voltage Measured on the breaker/section.
For a double pole breaker, it is the Li to Lj voltage.
cV
RO
PDU.Input[1].ActivePower
Measure
Active Power Measurement.
It is the accumulation of 1 or 3 phase measures.
dW
RO
PDU.Input[1].ApparentPower
Measure
Apparent Power Measurement.
It is the accumulation of 1 or 3 phase measures.
dVA
RO
PDU.Input[1].ChangedStatus.FrequencyOutOfRange
Timestamp
s
RO
PDU.Input[1].Frequency
Measure
Frequency Measurement.
dHz
RO
PDU.Input[1].Mode
Constant
Wiring Mode
0: Wye Measuring
1: Delta Measuring
2: Wye Current and Delta Measuring
-
RO
PDU.Input[1].Phase.Count
Constant
Number of phase managed by the Input module.
-
RO
PDU.Input[1].Phase[x].ActivePower
Measure
Active Power Measurement.
dW
RO
PDU.Input[1].Phase[x].ApparentPower
HideMeasure
Apparent Power Measurement.
dVA
RO
PDU.Input[1].Phase[x].ChangedStatus.OverCurrent
Timestamp
Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s
RO
PDU.Input[1].Phase[x].ChangedStatus.OverVoltage
Timestamp
Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s
RO
PDU.Input[1].Phase[x].Current
Measure
Current Measurement.
mA
RO
PDU.Input[1].Phase[x].OverCurrent[1].Threshold
Parameter
mA
RW
PDU.Input[1].Phase[x].OverCurrent[3].Threshold
Parameter
mA
RW
PDU.Input[1].Phase[x].OverCurrent[4].Threshold
Parameter
mA
RW
PDU.Input[1].Phase[x].OverVoltage[1].Threshold
Parameter
cV
RW
PDU.Input[1].Phase[x].OverVoltage[2].Threshold
Parameter
cV
RW
PDU.Input[1].Phase[x].OverVoltage[3].Threshold
Parameter
cV
RW
PDU.Input[1].Phase[x].OverVoltage[4].Threshold
Parameter
cV
RW
PDU.Input[1].Phase[x].PeakFactor
Measure
Crest factor of the current provided by the phase.
m%
RO
PDU.Input[1].Phase[x].PercentLoad
Measure
Percent load consumed on the phase. It is the ratio: current
consumed / the nominal current of the PDU.
%
RO
PDU.Input[1].Phase[x].PhaseID
Constant
Phase ID identifier depending of the wiring:
1: Line 1 to Neutral
2: Line 2 to Neutral
3: Line 3 to Neutral
12: Line 1 to Line 2
23: Line 2 to Line 3
31: Line 3 to Line 1
-
RO
PDU.Input[1].Phase[x].PowerFactor
HideMeasure
Ratio of active power / apparent power provided by the
phase.
Value 0 to 100 for Cos PHI = 0.00 to 1.00
m%
RO
Table 9. PDU CLI Objects (Continued)
XML Object Name
Type
Description
Unit
Access