LG LRSC26980TT Service Manual - Page 90
Cooling Cycle Heavy Repair
View all LG LRSC26980TT manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 90 highlights
TROUBLE DIAGNOSIS Cooling Cycle Heavy Repair 1. The Heavy Repair Standards for Refrigerator with R134a Refrigerant NO. Items Unit Standards Purposes Remarks 1 Pipe and piping system opening time. Min. Pipe:within 1 hour. To protect The opening time should be reduced to a Comp:within Moisture half of the standards during rain and 10 minutes. Penetration. rainy seasons (the penetration of water Drier:within into the pipe is dangerous). 20 minutes. 2 Welding. Nitrogen Pressure. Weld under Nitrogen atmosphere (N2 pressure: 0.1~0.2 kg/cm2) To protect oxide scale formation. - Refer to repair note in each part. - R134a refrigerant is more susceptible to leaks than R12 and requires more care during welding. - Do not apply force to pipes before and after welding to protect pipe from cracking. 3 N2 sealed parts. Confirm N2 leak. Confirm air leaking sounds when removing bushing cap. Sound:usable No sound:not usable To protect moisture penetration. - In case of evaporator parts, if it doesn't make noise when removing bushing cap blow dry air or N2 gas for more than 1 min use the parts. 4 Refrigeration Evacuation Cycle. time Min. More than 40 minutes. To remove moisture. Vacuum degree Torr Below 0.03(ref) Note:Only applicable to the model equipped with reverse flow protect plate. Vacuum EA High and low Pressure sides are evacuated at the L same time for models above 200 Vacuum efficiency can be improved by operating compressor during evacuation. Vacuum piping EA Use R134a exclusive manifold. To protect The bushing pipes for R12 refrigerant shall mixing of be melted when they are used for R134a mineral and refrigerant causes of leak. ester oils. Pipe coupler EA Use R134a cxclusive. To protect R12 Refrigerant mixing. Outlet (Socket) R134a exclusive. ˝ Plug 5 Refrigerant weighing. R134a exclusive ˝ EA Use R134a Do not mix - Do not weigh the refrigerant at too hot or exclusively. with R12 too cold an area. (25°C[77°F] is adequate.) Weighing refrigerant. - Use copper charging canister allowance:±5g Socket:2SV Plug: 2PV R134a Note:Winter:-5g Note : Do not burn O-ring (rubber) during Summer:+5g welding. 6 Drier replacement. -Use R134a exclusively To remove for R134a refrigerator the moisture -Replace drier whenever from pipe. repairing refrigerator cycle piping. 7 Leak check. -Do not use soapy water for check. It may be sucked into the pipe. Detect refrigerant leak area. -Check oil leak at refrigerant leak area. Use electronic leak detector if oil leak is not found. -The electronic leak detector is very sensitive to halogen gas in the air. It also can detect R141b in urethane. Please practice, therefore, many times before use. - 90 -