HP Superdome SX2000 User Service Guide, Seventh Edition - HP Integrity Superdo - Page 57
Airflow Diagram, Table 2-17 Physical Environmental Specifications, the top of the system.
View all HP Superdome SX2000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 57 highlights
NOTE: Approximately 5% of the system airflow draws from the rear of the system and exits the top of the system. Figure 2-2 Airflow Diagram A thermal report for the HP Integrity Superdome/sx2000 server is provided in Table 2-17 (page 57). Table 2-17 Physical Environmental Specifications Description Minimum Configuration Maximum Configuration Typical Configuration Condition Voltage 200-240 V ac Typical Heat Release Watts 3423 9130 6968 Nominal Airflow 2 Maximum Airflow at 32oC1,2 CFM m3/hr 2900 5.0 2900 5.0 2900 5.0 CFM m3/hr 2900 5.0 2900 5.0 2900 5.0 Weight pounds kg 926.3 420.3 1241.2 563.2 1135.2 515.1 Overall System Dimensions (W X D X H) in mm 30x48x77.2 76.2x121.9x195.6 30x48x77.2 76.2x121.9x195.6 30x48x77.2 76.2x121.9x195.6 ASHRAE Class 1 Minimum 2 Cell, 4 DIMM, 2 I/O Configuration3 Maximum 8 Cell, 32 DIMM, 4 I/O Configuration3 Typical 6 Cell, 16 DIMM, 4 I/O Configuration3 Environmental Requirements 57