Appendix A - ACE3600 Specifications 120/230V 12DO Relay Modules Total Number of Outputs 12 EE relay outputs 12 ML relay outputs Output Arrangement 12 x 1 Form A Contact Power Ratings 3A @ 250 V AC, 3A @ 30 V DC, or 0.20A @ 125 V DC (resistive load) Minimum Contact Load Current 10.0 mA @+5.00 V DC Maximum Switching Current 3.00 A Relay Back Indication Contact position - hardware back indication DO Frequency Max. 10 Hz (resistive load) Diagnostic LEDs LED per each output status, module error LED User Connection 3 Terminal Blocks (5.00mm pitch), Maximum 14 AWG Cable and TB Holder 30 Wire Cable with Terminal Block Holder connector, 20 AWG Fail State Configurable relay state on CPU fail: On, Off or 'last value' All Relays Disable/Enable Selectable per module, controlled from the power supply Module Replacement Hot swap replacement - module extraction/insertion under voltage Output Isolation Between output and module logic 2.5 kV per IEC60255-5 Insulation Insulation resistance 100 MΩ @ 500 V DC per IEC60255-5, Insulation impulse 5 kV per IEC60255-5 Operating Voltage 10.8-16 V DC and 3.3 V DC ±10% (from the motherboard connector) Power Consumption Refer to Appendix C: ACE3600 Maximum Power Ratings. Dimensions 37 mm W x 225 mm H x 180 mm D (1.5" W x 8.7" H x 7.1" D) Weight approx. 0.423 kg (0.90 lbs) Specifications subject to change without notice. 162