Motorola V186 User Manual - Page 170
Module error LED, Status LED per each DO and DI., Overflow and Underflow LED per each AI
View all Motorola V186 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 170 highlights
Appendix A - ACE3600 Specifications AI Interference Suppression Diagnostic LEDs 24 V DC Output User Connection Cable and TB Holder Module Replacement Input/Output Isolation Input Insulation Operating Voltage Power Consumption Selectable 50 or 60 Hz filtering, common mode rejection > 80 dB, differential mode rejection > 50 dB Module error LED, Status LED per each DO and DI. Overflow and Underflow LED per each AI, 24V Plug-in status LED (AI) AI Overflow and Underflow levels can be configured to: Current inputs: ±20mA / 4-20 mA Voltage inputs: ±5 V / 0-5 V /1-5 V Supports one isolated 24V plug-in "wetting" power supply 4 Terminal Blocks (3.5mm pitch), Maximum 18 AWG 40 wire cable with Terminal Block Holder connector, 26 AWG Hot swap replacement- module extraction/insertion under voltage DI: 2.5 kV RMS between input and module logic per IEC60255-5 DO: Between open contacts: 1kV, between output and module logic: 1.5 kV, per IEC60255-5 AI: 1.5 kV between input and module logic, per IEC60255-5 Insulation resistance 100 MΩ @ 500 V DC per IEC60255-5 10.8-16 V DC and 3.3 V DC (from the motherboard connector) Refer to Appendix C: ACE3600 Maximum Power Ratings. Dimensions Weight 37 mm W x 225 mm H x 180 mm D (1.5" W x 8.7" H x 7.1" D) Approx. 0.31 Kg (0.68 lb) Specifications subject to change without notice. 166