Toshiba T42F3F500XAMBN User Manual - Page 19

Installation Precautions

Page 19 highlights

TOSHIBA 3.0 Installation Precautions Based on the 4200FA UPS external dimensions and the way the outer panels are removed; minimum amounts of unobstructed space around the unit are necessary for ventilation and maintenance access. The following section and Fig. 3.1 shows the minimum clearances required for proper UPS site installation. 3.1 Equipment Placement 1) Do not install the UPS on an inclined surface, or areas that are subject to frequent vibrations or jolting. This could damage UPS circuits. 2) Do not allow liquids or foreign objects to get inside the UPS. REAR 6" (152mm) 3) Allow at least 20" (500 mm) on the front side and 6" (152 mm) on the rear and sides of the UPS unit for air ventilation and maintenance access. LEFT 6" (152mm) RIGHT 6" (152mm) 4) Do not install the UPS in a location that is subject to high humidity. Also, do not install the unit in areas that are exposed to direct sunlight, or contaminated areas subject to high levels of airborne dust, metal particles, or flammable gasses. 5) Verify the ventilation and air conditioning system at the site is capable of removing the heat generated by the UPS. FRONT 20" (500mm) Fig 3.1 Ambient temperature range for operating the UPS is 32 - 104 °F (0 - 40 °C); 77 °F (25 °C) is the recommended operating temperature for maximum battery life. 6) Avoid installation near sources of electrical noise. Always make sure that the unit's ground is intact to prevent electrical shock and help prevent electrical noise. 7) This UPS generates and radiates radiofrequency energy during operation. Although RFI noise filters are installed inside the unit there is no guarantee that the UPS will not influence some sensitive devices, which are operating in near proximity. If such interference occurs, the UPS should either be installed farther away from the affected equipment and/or powered from a different source than the affected equipment. 4200FA CT/XT User's Manual 18

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

TOSHIBA
3.0 Installation Precautions
Based on the 4200
FA
UPS external dimensions and the way the outer panels are removed; minimum
amounts of unobstructed space around the unit are necessary for ventilation and maintenance
access. The following section and Fig. 3.1 shows the minimum clearances required for proper UPS
site installation.
3.1
Equipment Placement
1)
2)
3)
4)
5)
6)
7)
Do not install the UPS on an inclined surface,
or areas that are subject to frequent vibrations
or jolting. This could damage UPS circuits.
LEFT
6” (152mm)
RIGHT
6” (152mm)
REAR
6” (152mm)
Do not allow liquids or foreign objects to get
inside the UPS.
Allow at least 20” (500 mm) on the front side
and 6" (152 mm) on the rear and sides of the
UPS unit for air ventilation and maintenance
access.
Do not install the UPS in a location that is
subject to high humidity.
Also, do not install
the unit in areas that are exposed to direct
sunlight, or contaminated areas subject to
high levels of airborne dust, metal particles, or
flammable gasses.
FRONT
20” (500mm)
Fig 3.1
Verify the ventilation and air conditioning
system at the site is capable of removing the
heat generated by the UPS.
Ambient temperature range for operating the
UPS is 32 – 104 °F (0 – 40 °C);
77 °F
(25 °C) is the recommended operating
temperature for maximum battery life.
Avoid installation near sources of electrical
noise. Always make sure that the unit's
ground is intact to prevent
electrical shock
and help prevent electrical noise.
This UPS generates and radiates radio-
frequency energy during operation. Although
RFI noise filters are installed inside the unit
there is no guarantee that the UPS will not
influence some sensitive devices, which are
operating in near proximity. If such
interference occurs, the UPS should either be
installed farther away from the affected
equipment and/or powered from a different
source than the affected equipment.
4200FA CT/XT User’s Manual