Toshiba T42F3F500XAMBN User Manual - Page 59
Backup History and Fault History
View all Toshiba T42F3F500XAMBN manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 59 highlights
TOSHIBA After the load is reduced, if the STOP/RUN key switch is in the RUN position, the UPS will automatically return to 'Inverter Operation' after a period of time. During this wait, the following screen will be displayed: - BYPASS OPERATION OUTPUT VOLTAGE=208 V CURRENT= 100/100/100 >PLEASE WAIT Or if the UPS is waiting and the STOP/RUN key switch is switched to the STOP position while the UPS is waiting, the following screen will be displayed: - BYPASS OPERATION OUTPUT VOLTAGE=208 V CURRENT= 100/100/100 >PLEASE WAIT If the STOP/RUN key switch remains in the STOP position when the UPS's 'wait' period is complete, then the following screen will be displayed: - BYPASS OPERATION OUTPUT VOLATAGE=###V CURRENT=100\100\100% DATE (DAY) TIME If the STOP/RUN key switch remains in the RUN position when the UPS's 'wait' period is complete, then the following screen will be displayed: - UPS ON-LINE OUTPUT VOLTAGE= 208 V CURRENT=100/100/99% DATE (DAY) TIME 6.21 Backup History and Fault History Pressing the MONI and F1 keys simultaneously, for a few seconds will cause the Battery Discharge Count screen to be displayed. BATT DISCHARGE COUNT # TIMES > F1: FOR DETAILS >Δ/∇: TO SCROLL Press the F1 key to display the record relating to the first discharge event. BACKUP HISTORY ( 1) #MIN##SEC VB=324V BT *PF OL >Δ/∇: EXIT F1: NEXT 4200FA CT/XT User's Manual 58