Control Circuit and External Interface Connections 50 kVA
View all Toshiba T42F3F500XAMBN manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 29 highlights
TOSHIBA 4.4 Control Circuit and External Interface Connections 50 kVA The following illustrates the wiring connections of the Control Circuits, and Battery Interface Circuits for the 50kVA. (15) Low Battery (16) Battery Discharge (17) Fault (18) Not Used (19) Inverter Supply (20) Inverter Supply (21) P24A3 (22) Remote Run (23) P24A3 (24) Remote Stop (25) Bypass (26) COMMON (27) EPO (28) EPO (3) Battery Shunt Trip (4) Battery Shunt Trip (5) Battery Aux. (6) Battery Aux. 4.4.1 Recommended Wire Size and Torque Requirements UPS Control and Battery Interface 50 kVA Minimum Wire Size and Torque Requirements UPS Control and Battery Interface Circuits USE MINIMUM 75 °C COPPER WIRING TERMINAL (TERMINAL #) AWG 50 kVA TIGHTENING TORQUE UPS CONTROL CIRCUITS (1-24)* 14-16 8 in-lbs. BATTERY CONTROL CIRCUITS (3-6)* 14-16 8 in-lbs. *Indicates Class 1 wiring methods are to be used. Maximum Wire Size is 12 AWG. 4200FA CT/XT User's Manual 28