Toshiba T42F3F500XAMBN User Manual - Page 34

kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries

Page 34 highlights

TOSHIBA 5.3 4200FA 30 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries Input Battery Output Environment Model Number Rated Output Capacity External Dimensions W x D x H (cm) Rated Voltage Voltage Variation Rated Frequency Input Cables required Dual Input Option Cables required * Power Factor Required Input kVA Walk-in Function Inrush Current Current Limit * Harmonic Currents DC Nominal (Voltage Range) Float Charge (Regulation) Ripple Voltage **Rated Back-up Time Rated Charge Current Rated Voltage Rated Current Rated Power Factor Output Cables Required Voltage Regulation (phase-phase) Voltage Adjustment Range Phase Displacement Rated Frequency Frequency Regulation Frequency Synchronous Frequency Slew Rate Voltage Transients (Recovery time: 50 ms) Inverter Overload Capacity Bypass Overload Capacity Crest Factor Neutral Line Conductor Harmonic Voltage Distortion Inrush Current protection Efficiency (Typical) Heat loss to be removed Audible Noise Operating Temperature Operating Humidity Altitude *** T42F3F300XAMBN T42F3F300##MBN 30 kVA 20.0" x 36.3" x 59.7" (50.8 cm x 92.2 cm x 151.6 cm) 208 VAC +10% to -30%; (-15% to -30%) 50 / 60 Hz 3 phase ; 4 Wire + GND 3 phase ; 4 Wire + GND Greater than 0.98 when in inverter mode 28.0 kVA From 20% to 100% over 5 seconds Less than 8 times the rated current under synchronous operation 115% maximum Less than 3% THD 288 VDC (216 to 332 VDC) 324.0 VDC (± 2%) 0.5 V R.M.S. 4 min at full load 4.0 Amps 208 / 120 VAC 83.4 Amps 0.8 lagging 3 phase ; 4 Wire + GND ± 2% (0-100% balanced load); ± 3% (0-100% unbalanced load) ± 5V Manually from the key pad ± 2° (0-100% balanced load); ± 4° (unbalanced load) 50 / 60 Hz ± 0.1% in free running mode ± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified technician 1 Hz/s to 3Hz/s (in 0.5 Hz steps) ± 5% (100% load step change); ± 3% (loss or return of input voltage); ± 8% (transfer of bypass to inverter) 125% 90 sec; 150% 30 sec 1000% 10 ms; 125% 10 min. 2.5-3.0 within the kW range 1.73 (200%) times line rating 1.5% max (linear load) Automatic Transfer to bypass, then retransfer to inverter AC/DC/AC: 85%; DC/AC: 87% 13,234 BTU/hr (3,334 kcal/hr) 60dB (A) at 1 meter from the front of the unit 32-104 °F (0 - 40 °C); optimal temperature is 77 °F (25 °C) 30-90% RH (non condensing) Less than 6600 ft (2000 m) Items marked with an (*) are specified at rated conditions under balanced linear loads. (**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. (***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). 4200FA CT/XT User's Manual 33

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

TOSHIBA
5.3
4200
FA
30 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries
Model Number
Rated Output Capacity
T42F3F300XAMBN
T42F3F300##MBN
30 kVA
External Dimensions
W x D x H
(cm)
20.0” x 36.3” x 59.7”
(50.8 cm x 92.2 cm x 151.6 cm)
Rated Voltage
208 VAC
Voltage Variation
+10% to -30%; (-15% to -30%)
Rated Frequency
50 / 60 Hz
Input Cables required
3 phase ; 4 Wire + GND
Dual Input Option Cables required
3 phase ; 4 Wire + GND
* Power Factor
Greater than 0.98 when in inverter mode
Required Input kVA
28.0 kVA
Walk-in Function
From 20% to 100% over 5 seconds
Inrush Current
Less than 8 times the rated current under synchronous operation
Current Limit
115% maximum
Input
* Harmonic Currents
Less than 3% THD
DC Nominal (Voltage Range)
288 VDC (216 to 332 VDC)
Float Charge (Regulation)
324.0 VDC (
±
2%)
Ripple Voltage
0.5 V R.M.S.
**Rated Back-up Time
4 min at full load
Battery
Rated Charge Current
4.0 Amps
Rated Voltage
208 / 120 VAC
Rated Current
83.4 Amps
Rated Power Factor
0.8 lagging
Output Cables Required
3 phase ; 4 Wire + GND
Voltage Regulation (phase-phase)
±
2% (0–100% balanced load);
±
3% (0–100% unbalanced load)
Voltage Adjustment Range
±
5V Manually from the key pad
Phase Displacement
±
2
°
(0–100% balanced load);
±
4
°
(unbalanced load)
Rated Frequency
50 / 60 Hz
Frequency Regulation
±
0.1% in free running mode
Frequency Synchronous
±
0.5/1.0/1.5 Hz (
±
1.0 Hz. std.)
switch selectable by qualified technician
Frequency Slew Rate
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
Voltage Transients
(Recovery time: 50 ms)
±
5% (100% load step change);
±
3% (loss or return of input voltage);
±
8% (transfer of bypass to inverter)
Inverter Overload Capacity
125% 90 sec; 150% 30 sec
Bypass Overload Capacity
1000% 10 ms; 125% 10 min.
Crest Factor
2.5–3.0 within the kW range
Neutral Line Conductor
1.73 (200%) times line rating
Harmonic Voltage Distortion
1.5% max (linear load)
Output
Inrush Current protection
Automatic Transfer to bypass, then retransfer to inverter
Efficiency (Typical)
AC/DC/AC: 85%; DC/AC: 87%
Heat loss to be removed
13,234 BTU/hr
(3,334 kcal/hr)
Audible Noise
60dB (A) at 1 meter from the front of the unit
Operating Temperature
32–104
°
F (0 – 40
°
C); optimal temperature is 77
°
F (25
°
C)
Operating Humidity
30–90% RH (non condensing)
Environment
Altitude ***
Less than 6600 ft (2000 m)
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
4200FA CT/XT User’s Manual
33