Toshiba T42F3F500XAMBN User Manual - Page 23

Recommended Wire Size and Torque Requirements

Page 23 highlights

TOSHIBA 4.1.3 Recommended Wire Size and Torque Requirements UPS Input and Output Terminals Minimum Wire Size and Torque Requirements UPS Input and Output Terminals 15/25/30 kVA (USE MINIMUM 75 °C INSULATED COPPER WIRING) Phase: (A) (B) (C) 15 kVA 25 kVA 30 kVA Input: (H1) (H2) (H3) AWG Torque AWG Torque AWG Torque 208 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 220 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 240 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 380 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 400 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 415 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 480 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 600 V 10 35 in-lbs. 10 35 in-lbs. 10 35 in-lbs. All wire sizes are per the NEC. Maximum Wire Size is 2 AWG. Output: (L1) (L2) (L3) (N) 120/208 V 127/220 V 240 V AWG (L1)(L3) 8 8 8 15 kVA AWG (N) Torque (inch-lbs.) (L1)-(L3) (N) 4 51 51 4 51 51 N/A 51 N/A AWG (L1)(L3) 4 4 4 25 kVA AWG (N) Torque (inch-lbs.) (L1)-(L3) (N) 2 51 87 2 51 87 N/A 51 N/A AWG (L1)(L3) 2 2 2 30 kVA AWG (N) Torque (inch-lbs.) (L1)-(L3) (N) 2 87 87 2 87 87 N/A 87 N/A 220/380 V 10 8 35 51 8 4 51 51 6 2 51 87 230/400 V 10 8 35 51 8 4 51 51 6 2 51 87 240/415 V 10 8 35 51 8 4 51 51 6 2 51 87 277/480 V 10 8 35 51 8 6 51 51 6 2 51 87 600 V 10 N/A 35 N/A 10 N/A 35 N/A 10 N/A 35 N/A Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size is 2 AWG. 15 kVA Input/ Output (GND) AWG Torque (G) 10 35 in-lbs. Maximum Wire Size is 2 AWG. 25 kVA AWG Torque 8 51 in-lbs. 30 kVA AWG Torque 6 51 in-lbs. Minimum Wire Size and Torque Requirements UPS Optional Separate Bypass Input "TB4" 15 / 25kVA (USE MINIMUM 75 °C INSULATED COPPER WIRING) Phase: (A) (B) (C) 15 kVA 25 kVA 30 kVA Input: (H1) (H2) (H3) AWG Torque AWG Torque AWG Torque 208 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 220 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 240 V 8 51 in-lbs. 4 51 in-lbs. 2 87 in-lbs. 380 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 400 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 415 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 480 V 10 35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. 600 V 10 35 in-lbs. 10 35 in-lbs. 10 35 in-lbs. Maximum Wire Size is 2 AWG. 4200FA CT/XT User's Manual 22

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

TOSHIBA
4.1.3
Recommended Wire Size and Torque Requirements
UPS Input and Output Terminals
Minimum Wire Size and Torque Requirements
UPS Input and Output Terminals 15/25/30 kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
15 kVA
25 kVA
30 kVA
Phase:
(A)
(B)
(C)
Input: (H1) (H2) (H3)
AWG
Torque
AWG
Torque
AWG
Torque
208 V
8
51 in-lbs.
4
51 in-lbs.
2
87 in-lbs.
220 V
8
51 in-lbs.
4
51 in-lbs.
2
87 in-lbs.
240 V
8
51 in-lbs.
4
51 in-lbs.
2
87 in-lbs.
380 V
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
400 V
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
415 V
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
480 V
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
600 V
10
35 in-lbs.
10
35 in-lbs.
10
35 in-lbs.
All wire sizes are per the NEC.
Maximum Wire Size is 2 AWG.
15 kVA
25 kVA
30 kVA
Output:
(L1) (L2) (L3) (N)
AWG
(L1)-
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3)
(N)
AWG
(L1)-
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3)
(N)
AWG
(L1)-
(L3)
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3)
(N)
120/208 V
8
4
51
51
4
2
51
87
2
2
87
87
127/220 V
8
4
51
51
4
2
51
87
2
2
87
87
240 V
8
N/A
51
N/A
4
N/A
51
N/A
2
N/A
87
N/A
220/380 V
10
8
35
51
8
4
51
51
6
2
51
87
230/400 V
10
8
35
51
8
4
51
51
6
2
51
87
240/415 V
10
8
35
51
8
4
51
51
6
2
51
87
277/480 V
10
8
35
51
8
6
51
51
6
2
51
87
600 V
10
N/A
35
N/A
10
N/A
35
N/A
10
N/A
35
N/A
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC.
Maximum Wire Size is 2
AWG.
15 kVA
25 kVA
30 kVA
Input/ Output (GND)
AWG
Torque
AWG
Torque
AWG
Torque
(G)
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
Maximum Wire Size is 2 AWG.
Minimum Wire Size and Torque Requirements
UPS Optional Separate Bypass Input “TB4” 15 / 25kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
15 kVA
25 kVA
30 kVA
Phase:
(A)
(B)
(C)
Input: (H1) (H2) (H3)
AWG
Torque
AWG
Torque
AWG
Torque
208 V
8
51 in-lbs.
4
51 in-lbs.
2
87 in-lbs.
220 V
8
51 in-lbs.
4
51 in-lbs.
2
87 in-lbs.
240 V
8
51 in-lbs.
4
51 in-lbs.
2
87 in-lbs.
380 V
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
400 V
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
415 V
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
480 V
10
35 in-lbs.
8
51 in-lbs.
6
51 in-lbs.
600 V
10
35 in-lbs.
10
35 in-lbs.
10
35 in-lbs.
Maximum Wire Size is 2 AWG.
4200FA CT/XT User’s Manual
22