Toshiba T42F3F500XAMBN User Manual - Page 41
Battery Backup Time and Discharge Process, Battery Low Voltage Tolerances, Models, 25/30/50 kVA
View all Toshiba T42F3F500XAMBN manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 41 highlights
TOSHIBA 6.5 Battery Backup Time and Discharge Process The UPS system, when used in conjunction with a TOSHIBA designed Battery System, is designed to provide several minutes of back-up time (Refer to the Battery System Manual for back-up times). These times are valid when the unit is operating under full load. When these models are operating at half load, the batteries can provide approximately 2 times the specified value. The exact length of these times will depend on the UPS model used, condition of the batteries, amount and type of load, temperature and other variables. CAUTION Contact TOSHIBA when using other than TOSHIBA designed Battery Systems to determine proper compliance. Using other systems could void Warranty and or Safety Certifications. The following illustration graphically shows the battery discharge process at full load conditions. 6.6 Battery Low Voltage Tolerances Excessive discharge will cause the UPS battery voltage to drop bellow tolerable levels. The chart shown below lists the voltage level at which each UPS unit's low-voltage alarm will sound, and also at what level the low-voltage condition will cause the unit to automatically shut down. Models Nominal Voltage Alarm Voltage Shutdown Voltage min. 15/25/30/50 kVA 288 VDC 252 VDC 216 VDC 4200FA CT/XT User's Manual 40