Toshiba T42F3F500XAMBN User Manual - Page 46

Batt. Oh *or Mccb-b Open

Page 46 highlights

TOSHIBA 6.12.2 Line-2 System Fault Messages Line-2 fault messages are automatically displayed when a system fault is detected. LINE-2 MESSAGES Display Message Translation DCOC DC Over-current DCUB DC Unbalanced DCOV DC Over-voltage OH Overheat (internal) OL Output Overload VOUV Inverter Under-voltage VOOV Inverter Over-voltage 6.12.3 Line-3 System Messages Line-3 messages show load current information, and user selected instructions. 6.12.4 Line-4 System Messages Line-4 messages reflect the UPS operating conditions. Warning messages will be displayed when an abnormal operating condition occurs. The following chart shows the allowable Line-4 messages. LINE-4 MESAGES Displayed Message Translation PHEI I/O NOT SYNCHRONIZE * AUTOTRANSFER * * LOW BATTERY * * UPS OL: REDUCE LOAD * * DCOC * * DCOV * * DCUB * * OL * * FUSE * * INOV * * INUV * * BATT. OH *OR MCCB-B OPEN * MM/DD/YY (DAY) HH:MM * * TRANSFER INHIBITED * * ENTER FOR DETAILS * Displayed when Input Phase rotation has been wired in a counter-clockwise rotation. Displayed when input and output frequencies are not synchronized. (Abnormal) Displayed when Auto-transfer to Bypass is active (i.e. current limit reached). (Abnormal) Displayed when battery voltage is low (abnormal) or the UPS batteries have failed self-diagnostic test. (Abnormal) Displayed when UPS has tripped due to an overload condition. (Abnormal) Displayed when the UPS has an internal failure. (Abnormal) Displayed when the UPS has an internal DC bus over-voltage. (Abnormal) Displayed when the UPS has an internal DC bus unbalance referenced to Neutral. (Abnormal) Displayed when UPS has tripped due to an overload condition. (Abnormal) Displayed when an internal transistor fuse opens. Displayed when inverter output over-voltage has occurred. (Abnormal) Displayed when inverter output under-voltage has occurred. (Abnormal) Displayed when the optional battery over-temp sensor has activated, or if the external battery disconnect is open. (Verify TB3-5, 6) Displayed when none of the above abnormal conditions are present. (Normal) Displayed when key switch position is changed and frequency is not synchronized. (Abnormal) Displayed when a Fault or Faults have occurred. (Abnormal) 4200FA CT/XT User's Manual 45

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

TOSHIBA
6.12.2 Line-2 System Fault Messages
Line-2 fault messages are automatically displayed when a system fault is detected.
LINE-2 MESSAGES
Display Message
Translation
DCOC
DC Over-current
DCUB
DC Unbalanced
DCOV
DC Over-voltage
OH
Overheat (internal)
OL
Output Overload
VOUV
Inverter Under-voltage
VOOV
Inverter Over-voltage
6.12.3 Line-3 System Messages
Line–3 messages show load current information, and user selected instructions.
6.12.4 Line-4 System Messages
Line-4 messages reflect the UPS operating conditions. Warning messages will be
displayed when an abnormal operating condition occurs. The following chart shows the
allowable Line-4 messages.
LINE-4 MESAGES
Displayed Message
Translation
Displayed when Input Phase rotation has been wired
in a counter-clockwise rotation.
PHEI
Displayed when input and output frequencies are not
synchronized.
(Abnormal)
I/O NOT SYNCHRONIZE
Displayed when Auto-transfer to Bypass is active (i.e.
current limit reached).
(Abnormal)
* AUTOTRANSFER *
Displayed when battery voltage is low (abnormal) or
the UPS batteries have failed self-diagnostic test.
(Abnormal)
* LOW BATTERY *
Displayed when UPS has tripped due to an overload
condition.
(Abnormal)
* UPS OL: REDUCE LOAD *
Displayed when the UPS has an internal failure.
(Abnormal)
* DCOC *
Displayed when the UPS has an internal DC bus
over-voltage. (Abnormal)
* DCOV *
Displayed when the UPS has an internal DC bus
unbalance referenced to Neutral. (Abnormal)
* DCUB *
Displayed when UPS has tripped due to an overload
condition.
(Abnormal)
* OL *
Displayed when an internal transistor fuse opens.
* FUSE *
Displayed when inverter output over-voltage has
occurred. (Abnormal)
* INOV *
Displayed when inverter output under-voltage has
occurred. (Abnormal)
* INUV *
Displayed when the optional battery over-temp
sensor has activated, or if the external battery
disconnect is open. (Verify TB3-5, 6)
* BATT. OH *OR MCCB-B OPEN
Displayed when none of the above abnormal
conditions are present. (Normal)
* MM/DD/YY (DAY)
HH:MM *
Displayed when key switch position is changed and
frequency is not synchronized. (Abnormal)
* TRANSFER INHIBITED *
Displayed when a Fault or Faults have occurred.
(Abnormal)
* ENTER FOR DETAILS *
4200FA CT/XT User’s Manual