Toshiba T42F3F500XAMBN User Manual - Page 25

Control Circuit and External Battery Interface Connections 15/25/30 kvA

Page 25 highlights

TOSHIBA 4.2 Control Circuit and External Battery Interface Connections 15/25/30 kvA The following illustrates the wiring connections of the Control Circuits, and Battery Interface Circuits. (1) Low Battery (2) Battery Discharge (3) Fault (4) Not Used (5) Inverter Supply (6) Inverter Supply (7) P24A3 (8) Remote Run (9) P24A3 (10) Remote Stop (11) Bypass (12) COMMON (13) EPO (14) EPO Battery Connection (+) Positive (-) Negative (3) Battery Shunt Trip (4) Battery Shunt Trip (5) Battery Aux. (6) Battery Aux. 4.2.1 Recommended Wire Size and Torque Requirements UPS Control and Battery Interface 15/25/30 kVA Minimum Wire Size and Torque Requirements UPS Control and Battery Interface Circuits USE MINIMUM 75 °C COPPER WIRING TERMINAL (TERMINAL #) 15/25/30 kVA TIGHTENING AWG TORQUE UPS CONTROL CIRCUITS (1-24)* 14-16 8 in-lbs. BATTERY CONTROL CIRCUITS (3-6)* 14-16 8 in-lbs. BATTERY (+/-) 4 51 in-lbs. *Indicates Class 1 wiring methods are to be used. Maximum Wire Size for Control Circuits is 12 AWG. Maximum for Battery is 2 AWG. 4200FA CT/XT User's Manual 24

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

TOSHIBA
4.2
Control Circuit and External Battery Interface Connections 15/25/30 kvA
The following illustrates the wiring connections of the Control Circuits, and Battery Interface
Circuits.
4.2.1
Recommended Wire Size and Torque Requirements
UPS Control and Battery Interface 15/25/30 kVA
Minimum Wire Size and Torque Requirements
UPS Control and Battery Interface Circuits
USE MINIMUM 75 °C COPPER WIRING
15/25/30 kVA
TERMINAL
(TERMINAL #)
AWG
TIGHTENING
TORQUE
UPS CONTROL CIRCUITS
(1-24)*
14-16
8 in-lbs.
BATTERY CONTROL
CIRCUITS (3-6)*
14-16
8 in-lbs.
BATTERY
(+/-)
4
51 in-lbs.
*Indicates Class 1 wiring methods are to be used.
Maximum Wire Size for Control Circuits is 12
AWG.
Maximum for Battery is 2 AWG.
(1)
Low Battery
(
(3)
2)
Battery Discharge
Fault
(4)
Not Used
(5)
Inverter Supply
(6)
Inverter Supply
(7)
P24A3
(8)
Remote Run
(9)
P24A3
(10) Remote Stop
(11) Bypass
(12) COMMON
(13) EPO
(14) EPO
Battery Connection
(+)
Positive
Negative
(3) Battery Shunt Trip
(4) Battery Shunt Trip
(5) Battery Aux.
(-)
(6) Battery Aux.
4200FA CT/XT User’s Manual
24