Toshiba T42F3F500XAMBN User Manual - Page 25
Control Circuit and External Battery Interface Connections 15/25/30 kvA
View all Toshiba T42F3F500XAMBN manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 25 highlights
TOSHIBA 4.2 Control Circuit and External Battery Interface Connections 15/25/30 kvA The following illustrates the wiring connections of the Control Circuits, and Battery Interface Circuits. (1) Low Battery (2) Battery Discharge (3) Fault (4) Not Used (5) Inverter Supply (6) Inverter Supply (7) P24A3 (8) Remote Run (9) P24A3 (10) Remote Stop (11) Bypass (12) COMMON (13) EPO (14) EPO Battery Connection (+) Positive (-) Negative (3) Battery Shunt Trip (4) Battery Shunt Trip (5) Battery Aux. (6) Battery Aux. 4.2.1 Recommended Wire Size and Torque Requirements UPS Control and Battery Interface 15/25/30 kVA Minimum Wire Size and Torque Requirements UPS Control and Battery Interface Circuits USE MINIMUM 75 °C COPPER WIRING TERMINAL (TERMINAL #) 15/25/30 kVA TIGHTENING AWG TORQUE UPS CONTROL CIRCUITS (1-24)* 14-16 8 in-lbs. BATTERY CONTROL CIRCUITS (3-6)* 14-16 8 in-lbs. BATTERY (+/-) 4 51 in-lbs. *Indicates Class 1 wiring methods are to be used. Maximum Wire Size for Control Circuits is 12 AWG. Maximum for Battery is 2 AWG. 4200FA CT/XT User's Manual 24