Toshiba T42F3F500XAMBN User Manual - Page 35

kVA w/Internal Transformer

Page 35 highlights

TOSHIBA 5.4 4200FA 30 kVA w/Internal Transformer Input Battery Output Environment Model Number Rated Output Capacity External Dimensions W x D x H (cm) Input Output Rated Voltage Voltage Variation Rated Frequency Input Cables Required Dual Input Option Cables required * Power Factor Required Input kVA Walk-in Function Inrush Current Current Limit * Harmonic Currents DC Nominal (Voltage Range) Float Charge (Regulation) Ripple Voltage **Rated Back-up Time Rated Charge Current Rated Voltage Rated Current Rated Power Factor Output Cables Required Voltage Regulation (phase-phase) Voltage Adjustment Range Phase Displacement Rated Frequency Frequency Regulation Frequency Synchronous Frequency Slew Rate Voltage Transients (Recovery time: 50 ms) Inverter Overload Capacity Bypass Overload Capacity Crest Factor Neutral Line Conductor Harmonic Voltage Distortion Inrush Current protection Efficiency (Typical) Heat loss to be removed Audible Noise Operating Temperature Operating Humidity Altitude *** T42#3*300#AMXN # =(B: 208; H: 220; C: 240; N: 380-415; D: 480; M: 600) VAC *=(F: 208; H: 220 wye; J: 240; P: 380-415 wye; K: 480 wye: M:600) 30 kVA 20.0" x 36.3" x 59.7" (50.8 cm x 92.2 cm x 151.6 cm) 208; 220; 240; 380; 400; 415; 480; 600 VAC (Determined by Input Transformer internal to the unit) +10% to -30%; (-15% to -30%) 50/60 Hz 3 phase ; 3 Wire + GND 3 phase ; 4 Wire + GND Greater than 0.98 when in inverter mode 30.5 kVA From 20% to 100% over 5 seconds Less than 8 times the rated current under synchronous operation 115% maximum Less than 3% THD 288 VDC (216 to 332 VDC) 324.0 VDC (± 2%) 0.5 V R.M.S. Refer to Battery System Manual 10.0 Amps (Determined by Output Transformer internal to the unit) VA / Nominal Output Voltage / 1.73 0.8 lagging 3 phase ; 4 Wire + GND ± 5% (0-100% balanced load); ± 6% (0-100% unbalanced load) ± 5V Manually from key pad ± 2° (0-100% balanced load); ± 4° (unbalanced load) 50 / 60 Hz ± 0.1% in free running mode ± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified technician 1 Hz/s to 3Hz/s (in 0.5 Hz steps) ± 5% (100% load step change); ± 3% (loss or return of input voltage); ± 8% (transfer of bypass to inverter) 125% 90 sec; 150% 30 sec 1000% 10ms; 125% 10 min. 2.5-3.0 within the kW range 1.73 (200%) times line rating 1.5% max (linear load) Automatic Transfer to bypass, then retransfer to inverter AC/DC/AC: 77%; DC/AC: 83% 23,216 BTU/hr (5,849 kcal/hr) 60dB (A) at 1 meter from the front of the unit 32°-104° F (0°-40° C); optimal temperature is 77° F (25° C) 30-90% RH (non condensing) Less than 2000 meters Items marked with an (*) are specified at rated conditions under balanced linear loads. (**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. (***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). 4200FA CT/XT User's Manual 34

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

TOSHIBA
5.4
4200
FA
30 kVA w/Internal Transformer
Model Number
T42#3*300#AMXN
Input
# =
(B: 208; H: 220; C: 240; N: 380–415; D: 480; M: 600) VAC
Output
*=
(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye: M:600)
Rated Output Capacity
30 kVA
External Dimensions
W x D x H
(cm)
20.0” x 36.3” x 59.7”
(50.8 cm x 92.2 cm x 151.6 cm)
Rated Voltage
208; 220; 240; 380; 400; 415; 480; 600 VAC
(Determined by Input Transformer internal to the unit)
Voltage Variation
+10% to -30%; (-15% to -30%)
Rated Frequency
50/60 Hz
Input Cables Required
3 phase ; 3 Wire + GND
Dual Input Option Cables required
3 phase ; 4 Wire + GND
* Power Factor
Greater than 0.98 when in inverter mode
Required Input kVA
30.5 kVA
Walk-in Function
From 20% to 100% over 5 seconds
Inrush Current
Less than 8 times the rated current under synchronous operation
Current Limit
115% maximum
Input
* Harmonic Currents
Less than 3% THD
DC Nominal (Voltage Range)
288 VDC (216 to 332 VDC)
Float Charge (Regulation)
324.0 VDC (
±
2%)
Ripple Voltage
0.5 V R.M.S.
**Rated Back-up Time
Refer to Battery System Manual
Battery
Rated Charge Current
10.0 Amps
Rated Voltage
(Determined by Output Transformer internal to the unit)
Rated Current
VA / Nominal Output Voltage / 1.73
Rated Power Factor
0.8 lagging
Output Cables Required
3 phase ; 4 Wire + GND
Voltage Regulation (phase-phase)
±
5% (0-100% balanced load);
±
6% (0-100% unbalanced load)
Voltage Adjustment Range
±
5V Manually from key pad
Phase Displacement
±
2
°
(0–100% balanced load);
±
4
°
(unbalanced load)
Rated Frequency
50 / 60 Hz
Frequency Regulation
±
0.1% in free running mode
Frequency Synchronous
±
0.5/1.0/1.5 Hz (
±
1.0 Hz. std.)
switch selectable by qualified technician
Frequency Slew Rate
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
Voltage Transients
(Recovery time: 50 ms)
±
5% (100% load step change);
±
3% (loss or return of input voltage);
±
8% (transfer of bypass to inverter)
Inverter Overload Capacity
125% 90 sec; 150% 30 sec
Bypass Overload Capacity
1000% 10ms; 125% 10 min.
Crest Factor
2.5–3.0 within the kW range
Neutral Line Conductor
1.73 (200%) times line rating
Harmonic Voltage Distortion
1.5% max (linear load)
Output
Inrush Current protection
Automatic Transfer to bypass, then retransfer to inverter
Efficiency (Typical)
AC/DC/AC: 77%; DC/AC: 83%
Heat loss to be removed
23,216 BTU/hr
(5,849 kcal/hr)
Audible Noise
60dB (A) at 1 meter from the front of the unit
Operating Temperature
32
°
–104
°
F (0
°
–40
°
C); optimal temperature is 77
°
F (25
°
C)
Operating Humidity
30–90% RH (non condensing)
Environment
Altitude ***
Less than 2000 meters
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
4200FA CT/XT User’s Manual
34