Toshiba T42F3F500XAMBN User Manual - Page 61

UPS Protection System

Page 61 highlights

TOSHIBA 7.0 UPS Protection System 7.1 System Protection Features The preceding one-line schematic illustrates the electrical locations of the protection devices on all UPS models. Input Power Input Abnormal MBS Isolating XFMR MCCB Bypass Converter Inverter Overcurrent Low Batteryt Charger/ Chopper External Batteries Overcurrent Overload Output Power Overvoltage/ Undervoltage 7.2 System Protection Functions The following chart shows the built-in UPS fault protection functions on all models. Protection Item LCD Message Cause Operation Mode after Fault Audible Alarm Visible Alarm Relay Contact Alarm Auto-Retransfer Built-in UPS Fault Protection Functions Inverter Over-voltage Inverter Under-voltage (IVOV) (IVUV) UPS Overload INVERTER OVERVOLTAGE INVERTER UNDERVOLTAGE OUTPUT OVERLOAD Control Malfunction; Feedback Error Overload or short circuit at the load. Bypass Operation; Chopper and Inverter Stopped Inverter Overload: Transfer to bypass; Inverter stopped. Bypass Overload: Inverter, Chopper, and Bypass stopped. Yes: See Audible Alarm Functions Red Fault Lamp "on" Inverter OL: No Fault Lamp Bypass OL: Fault Lamp "on" Fault Relay closed; Bypass Relay closed Inverter OL: Bypass Relay closed Bypass OL: Bypass Relay open and Fault relay closed No Inverter OL: Yes, if bypass ok Bypass OL: No Protection Item LCD Message Cause Operation Mode after Fault Audible Alarm Visible Alarm Relay Contact Alarm Auto-Retransfer Low Battery Voltage (Level-1) Low Battery Voltage (Level-2) Inverter Output Current Limit Line-4 will read "BATTERY LOW" DC UNDERVOLTAGE OUTPUT OVERLOAD Battery Discharge Battery Shutdown Level reached Load Inrush current Battery Discharge Shutdown: No Output If Bypass ok, transfer to bypass; if not, current-limit mode Yes: See Audible Alarm Functions Battery Lamp Flickers NO NO Low Battery Relay closed Bypass Relay closed No Yes, if bypass ok 4200FA CT/XT User's Manual 60

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68

TOSHIBA
7.0 UPS Protection System
7.1
System Protection Features
The preceding one-line schematic illustrates the electrical locations of the protection
devices on all UPS models.
Converter
Inverter
Bypass
Charger/
Chopper
Isolating
XFMR
External
Batteries
Output
Power
MCCB
MBS
Input
Power
Overcurrent
Low Batteryt
Input Abnormal
Overcurrent
Overload
Overvoltage/
Undervoltage
7.2
System Protection Functions
The following chart shows the built-in UPS fault protection functions on all models.
Built-in UPS Fault Protection Functions
Protection Item
Inverter Over-voltage
(IVOV)
Inverter Under-voltage
(IVUV)
UPS Overload
LCD Message
INVERTER
OVERVOLTAGE
INVERTER
UNDERVOLTAGE
OUTPUT OVERLOAD
Cause
Control Malfunction; Feedback Error
Overload or short circuit at the load.
Operation Mode
after Fault
Bypass Operation; Chopper and Inverter Stopped
Inverter Overload: Transfer to bypass; Inverter
stopped.
Bypass Overload: Inverter, Chopper, and Bypass
stopped.
Audible Alarm
Yes: See Audible Alarm Functions
Visible Alarm
Red Fault Lamp “on”
Inverter OL: No Fault Lamp
Bypass OL: Fault Lamp “on”
Relay Contact
Alarm
Fault Relay closed; Bypass Relay closed
Inverter OL: Bypass Relay closed
Bypass OL: Bypass Relay open and Fault relay
closed
Auto-Retransfer
No
Inverter OL: Yes, if bypass ok
Bypass OL: No
Protection Item
Low Battery Voltage
(Level-1)
Low Battery Voltage
(Level-2)
Inverter Output Current Limit
LCD Message
Line-4 will read
“BATTERY LOW”
DC UNDERVOLTAGE
OUTPUT OVERLOAD
Cause
Battery Discharge
Battery Shutdown Level
reached
Load Inrush current
Operation Mode
after Fault
Battery Discharge
Shutdown:
If Bypass ok, transfer to bypass; if not, current-limit
mode
No Output
Audible Alarm
Yes: See Audible Alarm Functions
Visible Alarm
Battery Lamp Flickers
NO
NO
Relay Contact
Alarm
Low Battery Relay
closed
Bypass Relay closed
Auto-Retransfer
No
Yes, if bypass ok
4200FA CT/XT User’s Manual
60