Toshiba T42F3F500XAMBN User Manual - Page 21
Caution
View all Toshiba T42F3F500XAMBN manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 21 highlights
TOSHIBA 13) Additional warnings and notifications shall be posted at the equipment installation location as deemed required by Qualified Personnel. CAUTION When the UPS is in the Inverter mode, turning the breaker to the OFF position will cause the unit to go into the battery backup mode. The UPS will continue to provide power to the load. The unit must be in Bypass mode and then the breaker turned to the OFF position for the UPS to shut down power to the load. CAUTION Do not EPO (Emergency Power OFF) the UPS and then reset the breaker until the UPS has been fully discharged. The UPS could be damaged if the unit is not fully powered down before the breaker is reset. 4.0 UPS Connections 4.1 Power Connections 4.1.1 Power Connections 15/25/30 kVA with Internal Batteries The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 15/25/30 kVA UPS Models CUSTOMER-PROVIDED AC DISTRIBUTION PANEL TB1 Optional Bypass Input: 3-phase, 3-Wire *208 V requires 3-phase, TB4 4-Wire Wye INPUT GROUND RESISTANCE LESS THAN 10 OHMS 4200FA CT/XT User's Manual 20