Xerox 6180N DocuSP 61xx version 3.6 - Installation Planning Guide - Page 28

The power lines that provide electrical service for the, DocuTech printer can not be shared

Page 28 highlights

Select and prepare an installation site NOTE: The power lines that provide electrical service for the DocuTech printer can not be shared with other devices. Electrical requirements for 60 hertz systems The type of electrical service that is installed depends on the existing electrical service, and the power cord configuration that works for your location. All configurations require a 110 VAC, 15 amp receptacle for the outlet strip that provides receptacles for the controller and its peripheral devices (monitor, modem, cdrom drive, and tape drive). A single power cable is the default configuration for the DocuTech 6100, 6115, or 6135 printer. This configuration consists of one single-phase (two lines and neutral, plus ground, four wire system, 50 amp outlet. • Line to neutral: 120V (nominal); range 107 VAC to 127 VAC • Line to neutral: 240V (nominal); range 205 VAC to 254 VAC The following kit is available through your Xerox representative: 600S3779: for the 50 amp receptacle kit. Required electrical service The following electrical service options are available: • Only available in DMO Latin 3-phase, single power cord configuration This configuration consists of one 120/208 VAC, 4 wires plus ground, 50 amp, 3-phase power cord. The following kits must be ordered through your Xerox representative: - 600K59310: for a wall mounted receptacle. - 600K59300: for a drop receptacle. - 98K59570: contains a 3-phase, single power cord and associated components. • For the USA and Canada only: 2-phase, dual power cord configuration 4-10 DocuTech 61xx Installation Planning Guide

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60

Select and prepare an installation site
4-10
DocuTech 61xx Installation Planning Guide
NOTE:
The power lines that provide electrical service for the
DocuTech printer can not be shared with other devices.
Electrical requirements for 60 hertz systems
The type of electrical service that is installed depends on the
existing electrical service, and the power cord configuration that
works for your location.
All configurations require a 110 VAC, 15 amp receptacle for the
outlet strip that provides receptacles for the controller and its
peripheral devices (monitor, modem, cdrom drive, and tape
drive).
A single power cable is the default configuration for the
DocuTech 6100, 6115, or 6135 printer.
This configuration consists of one single-phase (two lines and
neutral, plus ground, four wire system, 50 amp outlet.
Line to neutral:
120V (nominal); range 107 VAC to 127 VAC
Line to neutral:
240V (nominal); range 205 VAC to 254 VAC
The following kit is available through your Xerox representative:
600S3779:
for the 50 amp receptacle kit.
Required electrical service
The following electrical service options are available:
Only available in
DMO Latin
3-phase, single power cord
configuration
This configuration consists of one 120/208 VAC, 4 wires plus
ground, 50 amp, 3-phase power cord. The following kits must
be ordered through your Xerox representative:
600K59310: for a wall mounted receptacle.
600K59300: for a drop receptacle.
98K59570: contains a 3-phase, single power cord and
associated components.
For the
USA and Canada only
: 2-phase, dual power cord
configuration