Xerox 6180N DocuSP 61xx version 3.6 - Installation Planning Guide - Page 29
Line to Line
UPC - 095205425307
View all Xerox 6180N manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 29 highlights
Select and prepare an installation site This configuration consists of one 120/208 VAC, 3 wires plus ground, 50 amp, 2-phase power, and one 120/208 VAC, 3 wires plus ground, 30 amp, 2-phase power cords. The following kits must be ordered through your Xerox representative: - 600S3779: for the 50 amp receptacle, 4 wires plus ground - 600S3277: for the 30 amp receptacle, 4 wires plus ground - 98K59580: contains a 2-phase, dual power cord and associated components Optional electrical service The following electrical service options are available: • If the system includes an optional Interposer module, a separate 120 VAC, 3 wire, 15 amp electrical service is required. The following kit must be ordered through your Xerox representative: - 600S3704: for the 15 amp receptacle kit. Electrical requirements for 50 hertz printers This section describes the electrical requirements for 50 hertz systems. 3-phase star ("Wye"), single power cord configuration • Dedicated line voltage - Line to Neutral 220 x 6% 230 x 6% 240 x 6% 250 x 6% - Line to Line 380 VAC (nominal) 400 VAC (nominal) 415 VAC (nominal) 440 VAC (nominal) • 4 wires plus ground DocuTech 61xx Installation Planning Guide 4-11