Dell PowerEdge T620 Owner's Manual - Page 132
Expanded Operating Temperature Restrictions, Storage Temperature
View all Dell PowerEdge T620 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 132 highlights
Environmental < 1% of annual operating hours Expanded Operating Temperature Restrictions Storage Temperature NOTE: Outside the standard operating temperature (10 °C to 35 °C), the system can operate down to 5 °C or up to 40 °C for a maximum of 10% of its annual operating hours. For temperatures between 35 °C and 40 °C, de-rate maximum allowable dry bulb temperature by 1 °C per 175 m above 950 m (1 °F per 319 ft). -5 °C to 45 °C at 5% to 90% RH with 26 °C dew point. NOTE: Outside the standard operating temperature (10 °C to 35 °C), the system can operate down to -5 °C or up to 45 °C for a maximum of 1% of its annual operating hours. For temperatures between 40 °C and 45 °C, de-rate maximum allowable dry bulb temperature by 1 °C per 125 m above 950 m (1 °F per 228 ft). • You must have six fans configured on your system. • Do not perform a cold startup below 5 °C. • The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft). • Express Flash is not supported. • GPU is not supported. • LRDIMM is not supported. • 130 W 4 Core processor, 135 W processors, and 150 W processors are not supported. • Non-redundant power supplies are not supported. • Non Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported. -40 °C to 65 °C (-40 °F to 149 °F) with a maximum temperature gradation of 20 °C per hour. 132