View all HP StorageWorks 2/64 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 42 highlights
3. Secure the chassis port side to the rack rails using two #10-32 x 5/8 inch screws on each side. SHR-2514A Figure 10 Securing the chassis port side to rack rails 4. Tighten the screws, and torque to 32 inch-pounds. See Figure 10 for screw locations. Reinstalling the chassis door 1. Verify that the spring-loaded pins on both door hinges are retracted (push levers into notches). 2. Align the door hinges with the chassis portion of the hinges. 3. Push the levers out of the notches to release the pins. 42 Installing and configuring the switch
Installing and configuring the switch
42
3.
Secure the chassis port side to the rack rails using two #10-32 x 5/8 inch screws on each
side.
Figure 10
Securing the chassis port side to rack rails
4.
Tighten the screws, and torque to 32 inch-pounds. See
Figure 10
for screw locations.
Reinstalling the chassis door
1.
Verify that the spring-loaded pins on both door hinges are retracted (push levers into
notches).
2.
Align the door hinges with the chassis portion of the hinges.
3.
Push the levers out of the notches to release the pins.
SHR-2514A