Intel S1200RP Technical Product Specification - Page 25

AC Input Requirement

Page 25 highlights

Intel® Server System R1000RP Family TPS Cable Type Amperage Rating Voltage Rating SJT 13 A 125 V Power Subsystem Figure 15. AC Power Cord 3.1.4 AC Input Requirement 3.1.4.1 Power Factor The PF shall align with server energy star 2.0 requirements. Power supplies must meet the minimum power factor requirements presented in the table below, for all loading conditions where the output power is greater than or equal to 75 watts. Table 6. Power Factor Output power Power factor 20% load 0.8 50% load 0.9 100% load 0.98 3.1.4.2 AC Input Voltage Specification The power module shall operate over the range and limits shown in the following table. Table 7. AC Input Voltage Range PARAMETER MIN RATED MAX Max Input AC Current Line Voltage (110) 90 Vrms 100-127 Vrms 140 Vrms 6 Arms1 Line Voltage (220) 180 Vrms 200-240 Vrms 264 Vrms 3 Arms2 Frequency 47 Hz 50/60 Hz 63 Hz Notes: 1. Maximum input current at low input voltage range shall be measured at 90VAC, at maximum load. 2. Maximum input current at high input voltage range shall be measured at 180VAC, at maximum load. 3. This requirement is not to be used for determining agency input current markings. 3.1.4.3 AC Line Isolation Requirements The power supply shall meet all safety agency requirements for dielectric strength. Additionally, power supply vendor must provide Intel with written confirmation of dielectric withstand test which includes voltage level, duration of test, and identification detailing how each power supply is marked to indicate that the dielectric withstand test is completed successfully. Transformers' isolation between primary and secondary windings must comply with the 3000Vac (4242VDC) Revision 1.2 Intel order number: G91532-003 15

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82

Intel
®
Server System R1000RP Family TPS
Power Subsystem
Revision 1.2
Intel
order number: G91532-003
15
Cable Type
SJT
Amperage Rating
13 A
Voltage Rating
125 V
Figure 15. AC Power Cord
3.1.4
AC Input Requirement
3.1.4.1
Power Factor
The PF shall align with server energy star 2.0 requirements. Power supplies must meet the
minimum power factor requirements presented in the table below, for all loading conditions
where the output power is greater than or equal to 75 watts.
Table 6. Power Factor
Output power
20% load
50% load
100% load
Power factor
0.8
0.9
0.98
3.1.4.2
AC Input Voltage Specification
The power module shall operate over the range and limits shown in the following table.
Table 7. AC Input Voltage Range
PARAMETER
MIN
RATED
MAX
Max Input AC Current
Line Voltage
(110)
90 Vrms
100-127 Vrms
140 Vrms
6 Arms1
Line Voltage
(220)
180 Vrms
200-240 Vrms
264 Vrms
3 Arms2
Frequency
47 Hz
50/60 Hz
63 Hz
Notes:
1.
Maximum input current at low input voltage range shall be measured at 90VAC, at maximum load.
2.
Maximum input current at high input voltage range shall be measured at 180VAC, at maximum load.
3.
This requirement is not to be used for determining agency input current markings.
3.1.4.3
AC Line Isolation Requirements
The power supply shall meet all safety agency requirements for dielectric strength. Additionally,
power supply vendor must provide Intel with written confirmation of dielectric withstand test
which includes voltage level, duration of test, and identification detailing how each power supply
is marked to indicate that the dielectric withstand test is
completed successfully. Transformers’
isolation between primary and secondary windings must comply with the 3000Vac (4242VDC)