Rheem RARL-JEC Installation Instructions - Page 14

ber of elbows or bends.

Page 14 highlights

TABLE 5 (-)ARL SUCTION LINE SIZING SUCTION LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL R-410A System Capacity Model Line Size Connection Size (Inch I.D.) [mm] Line Size (Inch O.D.) [mm] Suction Line Size Outdoor Unit ABOVE Indoor Coil (Cooling Only - Does not apply to Heat Pumps) Total Equivalent Length - Feet [m] 25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.1] 150 [45.72] -024 -036 -048 -060 3/4" [19.05] 3/4" [19.05] 7/8" [22.22] 7/8" [22.22] 5/8" [15.88] 3/4" [19.05]* 7/8" [22.23] 5/8" [15.88] 3/4" [19.05]* 7/8" [22.23] 5/8" [15.88] 3/4" [19.05] 7/8" [22.23]* 3/4" [19.05] 7/8" [22.23]* 1-1/8" [28.58] Same as Liquid Line Size Table N/A N/A Same as Liquid Line Size Table N/A N/A Same as Liquid Line Size Table Same as Liquid Line Size Table Same as Liquid Line Size Table Same as Liquid Line Size Table Same as Liquid Line Size Table N/A NOTES: Using suction line larger than shown in chart will result in poor oil return. N/A = Application Not Recommended *Standard Line Size SUCTION LINE SIZE - OUTDOOR UNIT BELOW INDOOR COIL R-410A System Capacity Model Line Size Connection Size (Inch I.D.) [mm] Line Size (Inch O.D.) [mm] Suction Line Size Outdoor Unit BELOW Indoor Coil (Cooling Only - Does not apply to Heat Pumps) Total Equivalent Length - Feet [m] 25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.1] 150 [45.72] -024 -036 -048 -060 3/4" [19.05] 3/4" [19.05] 7/8" [22.22] 7/8" [22.22] 5/8" [15.88] 3/4" [19.05]* 7/8" [22.23] 5/8" [15.88] 3/4" [19.05]* 7/8" [22.23] 5/8" [15.88] 3/4" [19.05] 7/8" [22.23]* 3/4" [19.05] 7/8" [22.23]* 1-1/8" [28.58] Same as Liquid Line Size Table Same as Liquid Line Size Table N/A N/A Same as Liquid Line Size Table Same as Liquid Line Size Table N/A Same as Liquid Line Size Table Same as Liquid Line Size Table Same as Liquid Line Size Table Same as Liquid Line Size Table Same as Liquid Line Size Table N/A NOTES: Using suction line larger than shown in chart will result in poor oil return. N/A = Application Not Recommended *Standard Line Size • If tubing has been cut, make sure ends are deburred while holding in a position to prevent chips from falling into tubing. Burrs such as those caused by tubing cutters can affect performance dramatically, particularly on small liquid line sizes. • For best operation, keep tubing run as short as possible with a minimum number of elbows or bends. • Locations where the tubing will be exposed to mechanical damage should be avoided. If it is necessary to use such locations, the copper tubing should be housed to prevent damage. • If tubing is to be run underground, it must be run in a sealed watertight chase. • Use care in routing tubing and do not kink or twist. Use a good tubing bender on the vapor line to prevent kinking. • Route the tubing using temporary hangers, then straighten the tubing and install permanent hangers. Line must be adequately supported. 14

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

14
TABLE 5
(-)ARL SUCTION LINE SIZING
SUCTION LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL
R-410A
System
Capacity
Model
Line Size
Connection
Size (Inch
I.D.) [mm]
Line Size
(Inch O.D.)
[mm]
Outdoor Unit
ABOVE
Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Total
Equivalent
Length - Feet [m]
5/8” [15.88]
Same as Liquid Line Size Table
-024
3/4” [19.05]
3/4” [19.05]*
N/A
7/8” [22.23]
N/A
5/8” [15.88]
Same as Liquid Line Size Table
-036
3/4” [19.05]
3/4” [19.05]*
N/A
7/8” [22.23]
N/A
5/8” [15.88]
Same as Liquid Line Size Table
-048
7/8” [22.22]
3/4” [19.05]
Same as Liquid Line Size Table
7/8” [22.23]*
Same as Liquid Line Size Table
3/4” [19.05]
Same as Liquid Line Size Table
-060
7/8” [22.22]
7/8” [22.23]*
Same as Liquid Line Size Table
1-1/8” [28.58]
N/A
25 [7.62]
50 [15.24]
75 [22.86]
100 [30.48]
125 [38.1]
150 [45.72]
Suction Line Size
SUCTION LINE SIZE - OUTDOOR UNIT BELOW INDOOR COIL
R-410A
System
Capacity
Model
Line Size
Connection
Size
(Inch I.D.)
[mm]
Line Size
(Inch O.D.)
[mm]
Outdoor Unit
BELOW
Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Total
Equivalent
Length - Feet [m]
5/8” [15.88]
Same as Liquid Line Size Table
-024
3/4” [19.05]
3/4” [19.05]*
Same as Liquid Line Size Table
N/A
7/8” [22.23]
N/A
5/8” [15.88]
Same as Liquid Line Size Table
-036
3/4” [19.05]
3/4” [19.05]*
Same as Liquid Line Size Table
7/8” [22.23]
N/A
5/8” [15.88]
Same as Liquid Line Size Table
-048
7/8” [22.22]
3/4” [19.05]
Same as Liquid Line Size Table
7/8” [22.23]*
Same as Liquid Line Size Table
3/4” [19.05]
Same as Liquid Line Size Table
-060
7/8” [22.22]
7/8” [22.23]*
Same as Liquid Line Size Table
1-1/8” [28.58]
N/A
25 [7.62]
50 [15.24]
75 [22.86]
100 [30.48]
125 [38.1]
150 [45.72]
Suction Line Size
If tubing has been cut, make sure ends are deburred while holding in a position
to prevent chips from falling into tubing. Burrs such as those caused by tubing
cutters can affect performance dramatically, particularly on small liquid line
sizes.
For best operation, keep tubing run as short as possible with a minimum num-
ber of elbows or bends.
Locations where the tubing will be exposed to mechanical damage should be
avoided. If it is necessary to use such locations, the copper tubing should be
housed to prevent damage.
If tubing is to be run underground, it must be run in a sealed watertight chase.
Use care in routing tubing and do not kink or twist. Use a good tubing bender
on the vapor line to prevent kinking.
Route the tubing using temporary hangers, then straighten the tubing and
install permanent hangers. Line must be adequately supported.
NOTES:
Using suction line larger than shown in chart will result in poor oil return.
N/A = Application Not Recommended
*Standard Line Size
NOTES:
Using suction line larger than shown in chart will result in poor oil return.
N/A = Application Not Recommended
*Standard Line Size