CONVENTIONAL THERMOSTAT WIRING 30 Second Minimum Run Timer • The ICC has a built in 30 second minimum unit run time. If a call for compressor operation is received by the ICC and the call is removed, the compressor will continue to operate for 30 seconds. The dual 7-segment LEDs will flash "c" or "C" while the minimum run timer is active. 1 Second Compressor/Fan Delay • The ICC starts/stops the outdoor fan one (1) second after the start/stop of the compressor upon a call for compressor operation to minimize current inrush and/or voltage drop. 11.10 Active Compressor Protection Mode • The ICC actively protects the compressor from harmful operation during a fault condition. • When the ICC detects a condition that could damage the compressor, the ICC will enter active protection mode and lockout compressor operation • The condition causing active protection must be resolved then the ICC can be reset to restart the system. • There are five (5) active protection modes: 1) Low Pressure Control Lockout • The ICC will display a flashing "L" followed by a flashing 21 when a low pressure control lockout occurs. • The ICC addresses low pressure control faults differently depending on the mode of unit operation (cooling or heating mode). Active Protection - Code L21 - Open low pressure control Cooling Mode • If the LPC opens three (3) times during the same call for cooling operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a L" on the dual 7-segment LEDs followed by a "21". IMPORTANT: This mode of active protection must be manually reset. 2) High Pressure Control Lockout • If the HPC opens three (3) times during the same call for unit operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a L" on the dual 7-segment LEDs followed by a "29". Active Protection - Code L29 - Open high pressure control IMPORTANT: This mode of active protection must be manually reset. 30

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

30
30 Second Minimum Run Timer
• The ICC has a built in 30 second minimum unit run time. If a call for compressor
operation is received by the ICC and the call is removed, the compressor will con-
tinue to operate for 30 seconds. The dual 7-segment LEDs will flash “c” or “C”
while the minimum run timer is active.
1 Second Compressor/Fan Delay
• The ICC starts/stops the outdoor fan one (1) second after the start/stop of the
compressor upon a call for compressor operation to minimize current inrush
and/or voltage drop.
11.10 Active Compressor Protection Mode
• The ICC actively protects the compressor from harmful operation during a fault
condition.
• When the ICC detects a condition that could damage the compressor, the ICC will
enter active protection mode and lockout compressor operation
• The condition causing active protection must be resolved then the ICC can be
reset to restart the system.
• There are five (5) active protection modes:
1) Low Pressure Control Lockout
• The ICC will display a flashing “L” followed by a flashing 21 when a low pressure
control lockout occurs.
• The ICC addresses low pressure control faults differently depending on the mode
of unit operation (cooling or heating mode).
Active Protection – Code L21 – Open low pressure control
Cooling Mode
• If the LPC opens three (3) times during the same call for cooling operation, the
ICC will lockout the compressor to keep it from continuing to operate and flash a
L” on the dual 7-segment LEDs followed by a “21”.
IMPORTANT:
This mode of active protection must be manually reset.
2) High Pressure Control Lockout
• If the HPC opens three (3) times during the same call for unit operation, the ICC
will lockout the compressor to keep it from continuing to operate and flash a L” on
the dual 7-segment LEDs followed by a “29”.
Active Protection – Code L29 – Open high pressure control
IMPORTANT:
This mode of active protection must be manually reset.
CONVENTIONAL THERMOSTAT WIRING