THERMOSTATIC EXPANSION VALVES SYMPTOMS Superheat is low to normal with low suction pressure POSSIBLE CAUSE Unequal evaporator circuit loading Low load or airflow entering evaporator coil Superheat and suction pressure fluctuate (valve is hunting) Expansion valve is oversized Sensing bulb is affected by liquid refrigerant or refrigerant oil flowing through suction line Unequal refrigerant flow through evaporator circuits Valve does not regulate at all Improper superheat adjustment (only possible with TEV having superheat adjustment) Moisture freezing and partially blocking TEV External equalizer line not connected or line plugged Sensing bulb lost its operating charge Valve body damaged during soldering or by improper installation CHECK OR REMEDIES Ensure air flow is equally distributed through evaporator Check for blocked distributor tubes Ensure blower is moving proper air CFM Remove/Correct any air flow restriction Install correct TEV Relocate sensing bulb in another position around the circumference of the suction line Ensure sensing bulb is located properly Check for blocked distributor tubes Replace TEV or adjust superheat Recover refrigerant, change filterdrier, evacuate system and recharge Connect equalizer line in proper location, or remove any blockage Replace TEV Replace TEV 45

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

45
THERMOSTATIC EXPANSION VALVES
SYMPTOMS
POSSIBLE CAUSE
CHECK OR REMEDIES
Superheat is low to normal
Unequal evaporator circuit loading
Ensure air flow is equally distributed
with low suction pressure
through evaporator
Check for blocked distributor
tubes
Low load or airflow entering
Ensure blower is moving proper air
evaporator coil
CFM
Remove/Correct any air flow
restriction
Superheat and suction
Expansion valve is oversized
Install correct TEV
pressure fluctuate (valve is hunting)
Sensing bulb is affected by liquid
Relocate sensing bulb in another
refrigerant or refrigerant oil flowing
position around the circumference of
through suction line
the suction line
Unequal refrigerant flow through
Ensure sensing bulb is located
evaporator circuits
properly
Check for blocked distributor
tubes
Improper superheat adjustment
Replace TEV or adjust superheat
(only possible with TEV having
superheat adjustment)
Moisture freezing and partially
Recover refrigerant, change filter-
blocking TEV
drier, evacuate system and
recharge
Valve does not regulate at all
External equalizer line not connected
Connect equalizer line in proper
or line plugged
location, or remove any blockage
Sensing bulb lost its operating charge
Replace TEV
Valve body damaged during soldering
Replace TEV
or by improper installation