Rheem RARL-JEC Installation Instructions - Page 20
Active Compressor Protection Mode
View all Rheem RARL-JEC manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 20 highlights
COMFORT CONTROL2 SYSTEM™ CONTROL WIRING Flashing lower case c A command for first stage cooling has been received Flashing upper case C A command for second stage cooling has been received • The 3-minute time delay can be bypassed when a command for compressor operation is present by pressing the TEST button for 1 second and releasing. The compressor will begin operation and the dual 7-segment will stop flashing. 30 Second Minimum Run Timer • The ICC has a built in 30 second minimum unit run time. If a command for com- pressor operation is received by the ICC and the command is removed, the compressor will continue to operate for 30 seconds. The dual 7-segment LEDs will flash "c" or "C" while the minimum run timer is active. 1 Second Compressor/Fan Delay • The ICC starts/stops the outdoor fan one (1) second after the start/stop of the compressor upon a command for compressor operation to minimize current inrush and/or voltage drop. 11.4 Active Compressor Protection Mode • The ICC actively protects the compressor from harmful operation during a fault condition. • When the ICC detects a condition that could damage the compressor, the ICC will enter active protection mode and lockout compressor operation • The condition causing active protection must be resolved then the ICC can be reset to restart the system. • There are five (5) active protection modes: 1) Low Pressure Control Lockout • The ICC will display a flashing "L" followed by a flashing 21 when a low pressure control lockout occurs. • The ICC addresses low pressure control faults differently depending on the mode of unit operation (cooling or heating mode). Active Protection - Code L21 - Open low pressure control Cooling Mode • If the LPC opens three (3) times during the same command for cooling operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a L" on the dual 7-segment LEDs followed by a "21". IMPORTANT: This mode of active protection must be manually reset. 2) High Pressure Control Lockout • If the HPC opens three (3) times during the same command for unit operation, the ICC will lockout the compressor to keep it from continuing to operate and flash a L" on the dual 7-segment LEDs followed by a "29". 20