Rheem RARL-JEC Installation Instructions - Page 26

d4 - Device Memory Card Invalid

Page 26 highlights

Dual 7-Segment LEDs Display Code Diagnostic Description 29 - High Pressure Control Open The ICC detects the HPC is open LL29 - Active Protection High Pressure Control Trip Status/Possible Cause - Troubleshooting Information • Outdoor coil is dirty (cooling mode) • Outdoor fan is not running (cooling mode) • Dirty indoor coil or filter (heating mode) • Indoor blower is not running (heating mode) • Liquid line restriction • Excessive refrigerant charge LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29 FLASHING 30 - Fuse Open The ICC detects the on-board fuse is open 80 - Low Air Flow The ICC detects that the indoor unit is not providing the minimum airflow requirements. 83 - Condenser Coil Temperature Fault The sensor detects an abnormally low or high coil temperature 84 - Outdoor Ambient Temperature Fault The sensor detects an abnormally low or high outdoor ambient temperature 93 - Internal Control Fault The control is not functioning properly. d1 - No Shared Data d3 - Airflow CFM Mismatch The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation d4 - (Device) Memory Card Invalid for Device The data in the memory card inserted into the control board does not match the data in the control. d8 - Old Shared Data System data is obsolete • The 3-amp fuse on the ICC is open. • Low voltage wiring at R and C is damaged or miswired. • Misapplied/wrong indoor air mover - replace with properly sized unit. • Replace the sensor • Check sensor is installed correctly on control • Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. • Replace the sensor. • Check sensor is installed correctly on control • Check control for proper system operation. • Replace control • Replace memory card with correct system information. • Misapplied/wrong indoor air mover - replace with properly sized air handler/furnace. • Check memory card to ensure it matches device • Check if memory card is present • If system will not operate, order new memory card to update system information. 26

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

26
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
Status/Possible Cause – Troubleshooting
Information
29 – High Pressure Control Open
The ICC detects the HPC is open
• Outdoor coil is dirty (cooling mode)
• Outdoor fan is not running (cooling mode)
• Dirty indoor coil or filter (heating mode)
• Indoor blower is not running (heating mode)
• Liquid line restriction
• Excessive refrigerant charge
L29 –
Active Protection
High Pressure
Control Trip
LPC has opened 3 times in the same cooling
operation, the ICC has locked out the compressor
to protect it. ICC alternately flashes L and 29
FLASHING
80 – Low Air Flow
The ICC detects that the indoor unit is
not providing the minimum airflow
requirements.
• Misapplied/wrong indoor air mover –
replace with properly sized unit.
83 – Condenser Coil Temperature Fault
The sensor detects an abnormally low or
high coil temperature
• Replace the sensor
• Check sensor is installed correctly on control
84 – Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or
high outdoor ambient temperature
• Check unit placement – If the outdoor unit is in
a high temperature area, wait until the ambient
temperature drops and check sensor reading.
• Replace the sensor.
• Check sensor is installed correctly on control
93 – Internal Control Fault
The control is not functioning
properly.
• Check control for proper system
operation.
• Replace control
30 – Fuse Open
The ICC detects the on-board fuse is open
• The 3-amp fuse on the ICC is open.
• Low voltage wiring at R and C is damaged or
miswired.
d1 – No Shared Data
• Replace memory card with correct system
information.
d3 – Airflow CFM Mismatch
The indoor air mover (air
handler/furnace) cannot supply the
required airflow for proper system
operation
• Misapplied/wrong indoor air mover –
replace with properly sized air
handler/furnace.
d4 – (Device) Memory Card Invalid for
Device
The data in the memory card inserted
into the control board does not match
the data in the control.
• Check memory card to ensure it matches
device
• Check if memory card is present
d8 – Old Shared Data
System data is obsolete
• If system will not operate, order new
memory card to update system
information.