Rheem RARL-JEC Installation Instructions - Page 39

Cooling Mechanical Checks Flow Chart

Page 39 highlights

17.4 Cooling Mechanical Checks Flow Chart Unit Running? YES NO Pressure problems? Go to Electrical Checks Flow Chart High Head Pressure Low Head Pressure Low Suction Pressure Dirty Outdoor Coil Low on Charge Dirty Filters Inoperative Outdoor Fan Open IPR Valve Dirty Indoor Coil Overcharge Low Ambient Temperature Inadequate Indoor Air Flow Recirculation of Outdoor Air Inoperative Compressor Valves Inoperative Indoor Blower Non-condensibles Higher than Ambient Air Entering Outdoor Coil Wrong Outdoor Fan Rotation Outdoor Check Valve Closed Restricted Indoor Metering Device Low on Charge Restricted Indoor Metering Device Restriction in System Restricted Filter Drier Recirculation of Indoor Air Wrong Indoor Blower Rotation Inadequate Ducts Outdoor Check Valve Closed Restricted Filter Drier 39

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

39
Unit Running?
YES
NO
Go to Electrical
Pressure problems?
Checks Flow Chart
High Head Pressure
Low Head Pressure
Low Suction Pressure
Dirty Outdoor Coil
Low on Charge
Dirty Filters
Inoperative Outdoor Fan
Open IPR Valve
Dirty Indoor Coil
Overcharge
Low Ambient Temperature
Inadequate Indoor Air Flow
Recirculation of
Inoperative Compressor
Inoperative Indoor Blower
Outdoor Air
Valves
Non-condensibles
Outdoor Check Valve
Low on Charge
Closed
Higher than Ambient
Restricted Indoor
Air Entering Outdoor Coil
Metering Device
Restricted Indoor
Wrong Outdoor Fan Rotation
Metering Device
Restriction in System
Restricted
Recirculation of
Filter Drier
Indoor Air
Wrong Indoor
Blower Rotation
Inadequate Ducts
Outdoor Check Valve Closed
Restricted Filter Drier
17.4 Cooling Mechanical Checks Flow Chart