Rheem RARL-JEC Installation Instructions - Page 44

Thermostatic Expansion Valves

Page 44 highlights

THERMOSTATIC EXPANSION VALVES SYMPTOMS POSSIBLE CAUSE High Superheat, Low Suction Pressure Moisture freezing and blocking valve Dirt or foreign material blocking valve Low refrigerant charge Vapor bubbles in liquid line Valve feeds too much refrigerant, with low superheat and higher than mal suction pressure Misapplication of internally equalized valve Plugged external equalizer line Undersized TEV Loss of charge from power head sensing bulb Charge migration from sensing bulb to power head (Warm power head with warm, wet cloth. Does valve operate correctly now?) Improper superheat adjustment (Only applicable to TEV with adjustable superheat settings) Moisture causing valve to stick open. Dirt or foreign material causing valve to stick open TEV seat leak (A gurgling or hissing sound is heard AT THE TEV during the off cycle, if this is the cause.) NOT APPLICABLE TO BLEED PORT VALVES. Oversized TEV Incorrect sensing bulb location Compressor flood back upon start up Low superheat adjustment (only applicable to TEV with adjustable superheat setting) Incorrectly installed, or restricted external equalizer line Refrigerant drainage from flooded evaporator Compressor in cold location Any of the causes listed under Symptoms of Problem #2 CHECK OR REMEDIES Recover charge, install filter-drier, evacuate system, recharge Recover charge, install filter-drier, evacuate system, recharge Correct the charge Remove restriction in liquid line Correct the refrigerant charge Remove non-condensible gases Size liquid line correctly Use correct TEV Remove external equalizer line restriction Replace with correct valve Replace power head or complete TEV Ensure TEV is warmer than sensing bulb Adjust superheat setting counterclockwise Recover refrigerant, replace filterdrier, evacuate system and then norrecharge Recover refrigerant, replace filterdrier, evacuate system and recharge Replace the TEV Install correct TEV Install bulb with two mounting straps, in 2:00 or 4:00 position on suction line, with insulation Turn superheat adjustment clockwise Remove restriction, or relocate external equalizer Install trap riser to the top of the evaporator coil Install crankcase heater on compressor Any of the solutions listed under Solutions of Problem #2 44

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

44
THERMOSTATIC EXPANSION VALVES
SYMPTOMS
POSSIBLE CAUSE
CHECK OR REMEDIES
High Superheat, Low Suction Pressure
Moisture freezing and blocking valve
Recover charge, install filter-drier,
evacuate system, recharge
Dirt or foreign material blocking valve
Recover charge, install filter-drier,
evacuate system, recharge
Low refrigerant charge
Correct the charge
Vapor bubbles in liquid line
Remove restriction in liquid line
Correct the refrigerant charge
Remove non-condensible gases
Size liquid line correctly
Misapplication of internally equalized
Use correct TEV
valve
Plugged external equalizer line
Remove external equalizer line
restriction
Undersized TEV
Replace with correct valve
Loss of charge from power
Replace power head or complete
head sensing bulb
TEV
Charge migration from sensing bulb
Ensure TEV is warmer than
to power head (Warm power head
sensing bulb
with warm, wet cloth. Does valve
operate correctly now?)
Improper superheat adjustment
Adjust superheat setting counter-
(Only applicable to TEV with adjustable
clockwise
superheat settings)
Valve feeds too much refrigerant,
Moisture causing valve to stick open.
Recover refrigerant, replace filter-
with low superheat and higher than
drier, evacuate system and then nor-
mal suction pressure
recharge
Dirt or foreign material causing
Recover refrigerant, replace filter-
valve to stick open
drier, evacuate system and
recharge
TEV seat leak (A gurgling or hissing
Replace the TEV
sound is heard AT THE TEV during
the off cycle, if this is the cause.)
NOT APPLICABLE TO BLEED
PORT VALVES.
Oversized TEV
Install correct TEV
Incorrect sensing bulb location
Install bulb with two mounting
straps, in 2:00 or 4:00 position on
suction line, with insulation
Low superheat adjustment
Turn superheat adjustment
(only applicable to TEV with
clockwise
adjustable superheat setting)
Incorrectly installed, or restricted
Remove restriction, or relocate
external equalizer line
external equalizer
Compressor flood back upon start up
Refrigerant drainage from flooded
Install trap riser to the top of the
evaporator
evaporator coil
Compressor in cold location
Install crankcase heater on
compressor
Any of the causes listed under
Any of the solutions listed under
Symptoms of Problem #2
Solutions of Problem #2