Cisco 7206VXR Installation Guide - Page 81

Attaching a Grounding Lug to the Chassis Grounding Receptacles, Step 1

Page 81 highlights

Chapter 3 Installing the Cisco 7206 Providing a Chassis Ground Connection for the Router Chassis Use the following procedure to attach the grounding lug to the chassis grounding receptacles on your router chassis: Step 1 Step 2 Locate the chassis grounding receptacles on your router chassis. (See Figure 3-11.) Insert the two screws through the holes in the grounding lug. (See Figure 3-12.) Ensure that the grounding lug does not interfere with other router hardware, such as power supplies or the network processing engine. Figure 3-12 Attaching a Grounding Lug to the Chassis Grounding Receptacles Chassis grounding receptacles Screws Grounding lug Wire H10749 Step 3 Step 4 Step 5 Step 6 Step 7 Use the Phillips screwdriver to carefully tighten the screws until the grounding lug is held firmly to the chassis. Do not overtighten the screws. Use the wire stripper to strip one end of the 6-AWG wire approximately 0.75 inches (19.05 mm). Insert the 6-AWG wire into the wire receptacle on the grounding lug. (See Figure 3-12.) Use the crimping tool to carefully crimp the wire receptacle around the wire; this step is required to ensure a proper mechanical connection. Connect the opposite end of the grounding wire to the appropriate grounding point at your site to ensure an adequate chassis ground. This completes the procedure for providing a chassis ground connection. OL-5102-02 Cisco 7206 Installation and Configuration Guide 3-13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150

3-13
Cisco 7206 Installation and Configuration Guide
OL-5102-02
Chapter 3
Installing the Cisco 7206
Providing a Chassis Ground Connection for the Router Chassis
Use the following procedure to attach the grounding lug to the chassis grounding receptacles on your
router chassis:
Step 1
Locate the chassis grounding receptacles on your router chassis. (See
Figure 3-11
.)
Step 2
Insert the two screws through the holes in the grounding lug. (See
Figure 3-12
.) Ensure that the
grounding lug does not interfere with other router hardware, such as power supplies or the network
processing engine.
Figure 3-12
Attaching a Grounding Lug to the Chassis Grounding Receptacles
Step 3
Use the Phillips screwdriver to carefully tighten the screws until the grounding lug is held firmly to the
chassis. Do not overtighten the screws.
Step 4
Use the wire stripper to strip one end of the 6-AWG wire approximately 0.75 inches (19.05 mm).
Step 5
Insert the 6-AWG wire into the wire receptacle on the grounding lug. (See
Figure 3-12
.)
Step 6
Use the crimping tool to carefully crimp the wire receptacle around the wire; this step is required to
ensure a proper mechanical connection.
Step 7
Connect the opposite end of the grounding wire to the appropriate grounding point at your site to ensure
an adequate chassis ground.
This completes the procedure for providing a chassis ground connection.
H10749
Grounding lug
Wire
Chassis
grounding
receptacles
Screws