HP R1500 HP 3 Phase UPS User Guide - Page 104
Battery specifications, Battery runtimes
View all HP R1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 104 highlights
Feature Relative humidity Operating altitude Transit altitude Heat dissipation Audible noise Leakage current Surge suppression Safety conformance Specification Operating: 5% to 95%; noncondensing Non-operating: 5% to 95%; 38.7°C (101.7°F) maximum wet bulb temperature with no cosmetic damage Up to 1,000 m (3,300 ft) above sea level Up to 2,000 m (6,600 ft) with 1% derating per + 100 m (330 ft) UP to 15,000 m (49,000 ft) above sea level 1432 BTU/hr maximum at 100% rated load (High Efficiency Mode) 4094 BTU/hr maximum at 100% rated load (Standard Mode) Less than 58 dBA at 1 meter typical (Normal Mode) Less than 64 dBA at 1 meter typical (Battery Mode)
Specifications 104
Feature
Specification
Relative humidity
Operating:
5% to 95%; noncondensing
Non-operating:
5% to 95%; 38.7°C (101.7°F)
maximum wet bulb temperature with no cosmetic
damage
Operating altitude
Up to 1,000 m (3,300 ft) above sea level
Up to 2,000 m (6,600 ft) with 1% derating per + 100 m
(330 ft)
Transit altitude
UP to 15,000 m (49,000 ft) above sea level
Heat dissipation
1432 BTU/hr maximum at 100% rated load (High
Efficiency Mode)
4094 BTU/hr maximum at 100% rated load (Standard
Mode)
Audible noise
Less than 58 dBA at 1 meter typical (Normal Mode)
Less than 64 dBA at 1 meter typical (Battery Mode)
Leakage current
<3.5 mA
Surge suppression
ANSI C62.41 Category B3
Safety conformance
3 Phase UPS NA:
UL 1778 4th edition; CSA C22.2,
No. 107.1 and No. 107.3
3 Phase UPS INTL:
EN 60950-1 and IEC 62040-1-1
Agency Markings
3 Phase UPS NA:
UL/cUL
3 Phase UPS INTL:
CB, CE, GS, Ctick, GOST, BSMI
EMC (Class A)
3 Phase UPS NA:
FCC Part 15, ICES
3 Phase UPS INTL:
EN 62040-2
Battery specifications
Feature
Specification
Configuration
UPS internal batteries:
(40) 12 V, 5 Ah
+1 ERM:
(20) 12 V, 9 Ah
+2 ERMs:
(40) 12 V, 9 Ah
+3 ERMs:
(60) 12 V, 9 Ah
+4 ERMs:
(80) 12 V, 9 Ah
Type
Each model contains maintenance-free, sealed,
valve-regulated lead-acid batteries.
Monitoring
Advanced monitoring for earlier failure detection and
warning
Charging
8-10 times the discharge time. Complete charge takes no
more than 48 hours. Approximately 5 hours to 80 percent
capacity at default nominal utility voltage and no load.
Battery runtimes
Battery runtimes are approximate and vary depending on the load configuration and battery charge.