HP R1500 HP 3 Phase UPS User Guide - Page 79
Metering, UPS
View all HP R1500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 79 highlights
Metering The Output and Load Receptacle meter readings differ between a parallel system and a standalone UPS. In a parallel system, one UPS reads the Load Receptacle value for the total system (the others read zero), but each UPS displays its own Output value. For example, in a two-unit parallel system with one Anderson load connection for 12 kVA, the Load Receptacle current would read 12 kVA on one UPS and zero on the other UPS, but the Output measurement would be 6 kVA on each UPS (half the total). In a standalone UPS, the load can be connected from the outlet cord or the Anderson load connector. The Output measurement would be the total load on the UPS, and the Load reading would be the portion supplied by the Anderson load connector. Communication 79