HP R1500 HP 3 Phase UPS User Guide - Page 98

Protected equipment is not on, Overload condition, Overtemperature condition, Redundancy loss due

Page 98 highlights

4. To supply power to the connected equipment, power up the UPS. o Standalone UPS configuration-See "Powering up the standalone UPS (on page 25)." o Parallel UPS configuration-See "Powering up the parallel system (on page 39)." Protected equipment is not on Possible cause: The UPS is operating normally, but some or all of the protected equipment is not on. Action: • Be sure that the equipment is plugged into the UPS receptacles. • Be sure that the output circuit breaker is in the Off position. Overload condition Possible cause: Power requirements exceed the UPS capacity. For output overload ranges, see "UPS output specifications (on page 103)." Action: Remove one or more load devices to reduce the power requirements.The UPS continues to operate, but might switch to Auto-Bypass mode (on page 66) if the load increases. The alarm resets when the conditions becomes inactive. Overtemperature condition Possible cause: The UPS internal temperature is too high, or a fan has failed. Action: 1. Power down the UPS. o Standalone UPS configuration-See "Powering down the standalone UPS (on page 72)." o Individual UPS in a parallel configuration-See "Powering down an individual paralleled UPS (on page 72)." o Parallel UPS configuration-See "Powering down the parallel system (on page 73)." 2. Allow the UPS to cool: a. Clear vents and remove any heat sources. b. Be sure that the that the airflow around the UPS is not restricted. 3. Wait at least 5 minutes and restart the UPS. 4. If the condition persists, contact an HP authorized service representative. Redundancy loss due to overload Possible cause: The specified power rating of the parallel system has been exceeded. Action: The load is supported, but the system lacks redundant protection while the overload condition persists. Troubleshooting 98

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115

Troubleshooting 98
4.
To supply power to the connected equipment, power up the UPS.
o
Standalone UPS configuration—See "Powering up the standalone UPS (on page
25
)."
o
Parallel UPS configuration—See "Powering up the parallel system (on page
39
)."
Protected equipment is not on
Possible cause:
The UPS is operating normally, but some or all of the protected equipment is not on.
Action:
Be sure that the equipment is plugged into the UPS receptacles.
Be sure that the output circuit breaker is in the Off position.
Overload condition
Possible cause:
Power requirements exceed the UPS capacity. For output overload ranges, see "UPS output
specifications (on page
103
)."
Action
:
Remove one or more load devices to reduce the power requirements.The UPS continues to operate, but might
switch to Auto-Bypass mode (on page
66
) if the load increases.
The alarm resets when the conditions becomes inactive.
Overtemperature condition
Possible cause:
The UPS internal temperature is too high, or a fan has failed.
Action
:
1.
Power down the UPS.
o
Standalone UPS configuration—See "Powering down the standalone UPS (on page
72
)."
o
Individual UPS in a parallel configuration—See "Powering down an individual paralleled UPS (on
page
72
)."
o
Parallel UPS configuration—See "Powering down the parallel system (on page
73
)."
2.
Allow the UPS to cool:
a.
Clear vents and remove any heat sources.
b.
Be sure that the that the airflow around the UPS is not restricted.
3.
Wait at least 5 minutes and restart the UPS.
4.
If the condition persists, contact an HP authorized service representative.
Redundancy loss due to overload
Possible cause:
The specified power rating of the parallel system has been exceeded.
Action:
The load is supported, but the system lacks redundant protection while the overload condition persists.