HP R1500 HP 3 Phase UPS User Guide - Page 41

Configuring the Parallel UPS Card, Communication Bay 2.

Page 41 highlights

Configuring the Parallel UPS Card 1. Unpack the Parallel UPS Card, and be sure that the card was not damaged during shipment. NOTE: If installing another X-Slot card, be sure to install the Parallel UPS Card in X-Slot Communication Bay 2. 2. Remove the UPS X-Slot communication bay cover, and retain the screws. 3. Set the jumper pins on the Parallel UPS Card according to the parallel configuration. For three or more paralleled UPSs: o Set the cards of the first and last UPS to Pins 1 and 2. o Set the card for the middle UPS(s) to Pins 2 and 3. 4. Install the Parallel UPS Card into an open X-Slot on the rear of the UPS. 5. Repeat steps 1 through 4 to install a Parallel UPS Card into each UPS to be paralleled. The HP 3 Phase UPS parallel system automatically assigns identities to each UPS in the system based on the order in which their Parallel UPS Cards are wired. For more information, see "Auto-identification (on page 78)" . 6. Verify that all the terminal blocks and jumpers are installed in each UPS. 7. Using the supplied CAT 5 cables, install the Parallel UPS Card wiring between each UPS, connecting the card OUT port on one UPS to the card IN port on the next UPS. UPS installation 41

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115

UPS installation 41
Configuring the Parallel UPS Card
1.
Unpack the Parallel UPS Card, and be sure that the card was not damaged during shipment.
NOTE:
If installing another X-Slot card, be sure to install the Parallel UPS Card in X-Slot
Communication Bay 2.
2.
Remove the UPS X-Slot communication bay cover, and retain the screws.
3.
Set the jumper pins on the Parallel UPS Card according to the parallel configuration.
For three or more paralleled UPSs:
o
Set the cards of the first and last UPS to Pins 1 and 2.
o
Set the card for the middle UPS(s) to Pins 2 and 3.
4.
Install the Parallel UPS Card into an open X-Slot on the rear of the UPS.
5.
Repeat steps 1 through 4 to install a Parallel UPS Card into each UPS to be paralleled.
The HP 3 Phase UPS parallel system automatically assigns identities to each UPS in the system based on
the order in which their Parallel UPS Cards are wired. For more information, see "Auto-identification (on
page
78
)" .
6.
Verify that all the terminal blocks and jumpers are installed in each UPS.
7.
Using the supplied CAT 5 cables, install the Parallel UPS Card wiring between each UPS, connecting
the card OUT port on one UPS to the card IN port on the next UPS.