Heat Pump Reverse Cycle Heating Capacity
View all LG LP070HED1 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 49 highlights
Heat Pump Reverse Cycle Heating Capacity Model Voltage Amps Watts Btu/h COP CFM(Dry) Heating Btu/h Outdoor Ambient 62 57 52 Rating Point 47 42 37 32 27 24 Watts Outdoor Ambient 62 57 52 Rating Point 47 42 37 32 27 24 LP070HED1 265 2.2 550 6200 3.3 300 7200 6900 6500 6200 5900 5600 5300 5000 4800 580 575 555 550 540 525 515 510 505 LP090HED1 265 2.7 690 8000 3.4 300 9700 9200 8600 8000 7500 7000 6500 6000 5700 745 735 715 690 670 650 635 605 590 LP120HED1 265 3.9 990 10800 3.2 420 13100 12400 11600 10800 10100 9300 8500 7800 7400 1085 1055 1025 990 955 925 875 835 810 LP150HED1 265 5.3 1335 13200 2.9 420 15700 14900 14100 13200 12400 11600 10800 10000 9500 1425 1405 1370 1335 1300 1265 1220 1180 1170 Downloaded from www.Manualslib.com manuals search engine -49-