HP LH4r HP Netserver LP 1000r (1.13, 1.26 & 1.40 GHz) User Guide - Page 83
Attaching the Outer-Rail Assemblies, Location Marks on the Rack's Columns
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 83 highlights
Chapter 8 Rack Mounting the HP Netserver (4-Post) The screw holes cover a span of only one EIA unit, which is the height requirement of the HP Netserver. NOTE The Netserver can only be mounted into both holes of one EIA Unit, but cannot be mounted across two EIA units. You cannot use a hole in one EIA unit and a hole in another EIA unit. 2. Use the masking tape (or marking pen) to mark above the 3rd hole up on both front columns, as shown in Figure 8-3. Rear of Rack "#" represents the EIA unit numbers on the rack columns. 3rd Hole From Bottom Masking Tape Maker Left Side Mark this face of the columns with masking tape or marker pen. Right Side 1st Hole From Bottom Bottom of HP Netserver Front of Rack Figure 8-3. Location Marks on the Rack's Columns 3. Mark the inside face of the left-rear and right-rear rack columns as shown in Figure 8-3. Attaching the Outer-Rail Assemblies No tools are required to attach the outer-rail assemblies to the rack columns. 1. Pull the anti-tip foot forward out of the bottom of the rack. See Figure 8-4 for the anti-tip foot location. 2. Lower the leveler screws on the rack's lower four corners to make firm contact with the floor. See Figure 8-4. 3. Align the left outer-rail to the left front and rear columns as shown in Figure 8-4. 77