Sanyo 26KHHS72R Service Manual - Page 103
Wiring System Diagrams, Maximum Over Current Protection 15 A, Fuse Or Hacrtype Circuit Breaker
![]() |
View all Sanyo 26KHHS72R manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 103 highlights
1. Specifications Indoor Unit Type (B) Power Supply AWG #14 Trade Size of Conduit MOP (Fuse or HACR type circuit breaker) X, K, T, U Max. length 67 ft. 3/4 in. 15 A Control Wiring (C) Inter-Unit Control Wiring AWG #18 Use high voltage wire (300 V)*1 (D) Remote Control Wiring AWG #18*2 (0.75 mm2) (E) Control Wiring For Group Control AWG #18*2 - (0.75 mm2) Max. 3,300 ft. Max. 1,650 ft. Max. 1,650 - ft. (Total) *1 With ring-type wire terminal. *2 Wire joint connection. Wiring System Diagrams Basic wiring diagram for standard control Outdoor unit INV unit Indoor Inter-unit power line 208 / 230 V, 60 Hz A L1 L2 L1 Power supply L2 208 / 230 V, 60Hz unit B 1 1 Grounding line 1 2 2 Remote controller D WHT 1 1 BLK 2 2 G Grounding line C G U1 U1 U2 U2 Ground NOTE 2 1) Refer to " Recommended Wire Length and Wire Diameter for Power Supply System" for the explanation of "A", "B", "C", "D", and "E", in the above diagrams. CH Type 8P terminal board 2) Inter-Unit Control Wiring (C) and remote controller wiring (D), (E) have no polarity. But for other wiring, U1 U2 1 2 G L1 L2 3 respect polarity. Be sure to connect as shown in the Wiring System Diagram. Inter-unit Inter-unit Power wiring control wiring power wiring 3) In case of separate supply connection to indoor unit, over current protection must be provided between power source and indoor unit. X, T, U Type 5P terminal board MAXIMUM OVER CURRENT PROTECTION 15 A 4 (FUSE OR HACRTYPE CIRCUIT BREAKER) 1 2 G U1 U2 Inter-unit Inter-unit Remote power wiring control wiring controller wiring K Type 4P terminal board 5 I-99 U1 U2 1 2 G Inter-unit Inter-unit control wiring power wiring Remote controller wiring 6 SM831148
![](/manual_guide/products/sanyo-26khhs72r-service-manual-8912f5e/103.png)