1-2 Major Component Specifications 1. Specifications (A) Indoor Unit MODEL No. UH2672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan (Number ... diameter) in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFG4X - 71B6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole ... r.p.m. (230 V, High) rpm 4 ... 920 Nominal output W 100 Coil resistance Ω BRW - WHT : 74.7 , ORG - YEL : 9.59 (Ambient temperature 68 °F) WHT - VLT : 19.1 , YEL - BLK : 10.52 VLT - ORG : 10.5 , BLK - PNK : 21.72 Safety device Operating temperature Open °F 266 ± 14.4 Close °F 174.2 ± 27 Run capacitor VAC, µF 440 V , 5 µF 1 Heat exchanger Coil Aluminum plate fin / Copper tube Rows ... Fins per inch 3 ... 14.9 Face area ft.2 (m2) 2.03 (0.189) DATA SUBJECT TO CHANGE WITHOUT NOTICE 2 3 4 5 6 SM831148 I-35