Sanyo 26KHHS72R Service Manual - Page 175

Table of Self-Diagnostic Functions and Corrections X, T, U, K Type

Page 175 highlights

6-76.-7T.abTalebleofofSSeellff--DDiiaaggnnoossticticFuFnucntiocntisoannsdaCnodrreCcotiorrnesct(Xio, nT,sU(,XK, TTy,pUe,) K Type) VI-5 Wired remote Indoor unit controller display receiver lamp 1:1 connection (single type) Group connection Cause Simultaneous-operation multi system (flexible combination) Control by main-sub remote controllers Correction Nothing is displayed Nothing is displayed G Remote controller is not connected correctly. G Remote controller is not connected with G Same as at left G Indoor unit power is not ON. indoor unit correctly G Indoor unit power is not ON. G Same as at left Connect the remote controller correctly. Turn ON the indoor unit power. E 0 1 displayed Operating lamp E 0 2 displayed is blinking. E 0 9 displayed E 1 4 displayed G Automatic address setting has not been G Automatic address setting has not been G Same as at left completed. completed. G Inter-unit control wiring is cut or is not G Inter-unit control wiring is cut or is not connected correctly. connected correctly. G Remote controller is not connected correctly G Remote controller is not connected with (remote controller receiving failure). indoor unit correctly G Remote controller is not connected correctly G Remote controller is not connected with G Same as at left (failure in transmission from remote controller indoor unit correctly to indoor unit). G Same as at left Check the remote controller and inter-unit control wiring. Perform automatic address setting. G Same as at left Connect the remote controller correctly. G 2 remote controllers are Refer to 11-8-6 Main-sub remote control, and set as the main remote make the correct settings. controller. G Remote controller crossover wiring is cut or G Same as at left is not connected correctly. Check the remote controller crossover wiring. Perform automatic address setting again. E 0 4 displayed G Indoor-outdoor inter-unit wiring is not connected correctly. G Same as at left G Same as at left G Same as at left Connect the wiring correctly. E 0 6 displayed Standby lamp is blinking. E 1 5 displayed G Indoor unit capacity is too low. G Indoor-outdoor inter-unit wiring is cut or G Same as at left is not connected correctly. G Same as at left G Same as at left G Same as at left G Same as at left E 1 6 displayed G Indoor unit capacity is too high. E 2 0 displayed P 0 5 displayed L 0 2 displayed L 1 3 displayed L 0 7 displayed P 0 9 displayed G No serial signal is being received at all from the indoor units. Operation lamp and G Inter-unit circuit or open phase in the outdoor Standby lamp are unit power blinking alternately. G Insufficient gas Both the Operation G Indoor-outdoor unit type mismatch lamp and Standby lamp are blinking together. Timer lamp and G The indoor unit ceiling panel connector is not Standby lamp are connected correctly. blinking alternately. G Reversed phase or open phase in the 3-phase power at one of the outdoor units in the group G Same as at left G Ceiling panel connector at one of the indoor units in the group is not connected correctly. G Reversed phase or open phase in the outdoor unit 3-phase power G Same as at left G Same as at left G Remote controller crossover wiring is connected G Same as at left to the indoor unit, however it is set for individual operation. G Indoor unit ceiling panel connector is not G Same as at left connected correctly. Refer to 11-8 System Control, and make the correct settings. Check that the total capacities of the indoor and outdoor units are appropriate. Check that the indoor unit power is ON, and that the inter-unit control wiring is connected correctly. Reverse 2 phases of the outdoor unit 3-phase power and connect them correctly. Check that the indoor and outdoor unit types are correct. Perform automatic address setting. Connect the indoor unit ceiling panel connector correctly. 6. Test run SM831148 1 2 3 4 5 6

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180

VI-5
SM831148
6
6. Test run
Wired remote
controller display
Cause
Correction
Nothing is
displayed
Nothing is
displayed
E 0 1
displayed
E 0 2
displayed
E 0 9
displayed
E 1 4
displayed
E 0 4
displayed
E 0 6
displayed
E 1 5
displayed
E 1 6
displayed
E 2 0
displayed
P 0 5
displayed
L 0 2
displayed
L 1 3
displayed
P 0 9
displayed
L 0 7
displayed
Indoor unit
receiver lamp
Operating lamp
is blinking.
Standby lamp
is blinking.
Both the Operation
lamp and Standby
lamp are blinking
together.
Operation lamp and
Standby lamp are
blinking alternately.
Timer lamp and
Standby lamp are
blinking alternately.
Remote controller is not connected correctly.
Indoor unit power is not ON.
Automatic address setting has not been
completed.
Inter-unit control wiring is cut or is not
connected correctly.
Remote controller is not connected correctly
(remote controller receiving failure).
Remote controller is not connected correctly
(failure in transmission from remote controller
to indoor unit).
Indoor-outdoor inter-unit wiring is not
connected correctly.
Indoor unit capacity is too low.
Indoor unit capacity is too high.
No serial signal is being received at all from
the indoor units.
Inter-unit circuit or open phase in the outdoor
unit power
Insufficient gas
Indoor-outdoor unit type mismatch
The indoor unit ceiling panel connector is not
connected correctly.
Remote controller is not connected with
indoor unit correctly
Indoor unit power is not ON.
Automatic address setting has not been
completed.
Inter-unit control wiring is cut or is not
connected correctly.
Remote controller is not connected with
indoor unit correctly
Remote controller is not connected with
indoor unit correctly
Same as at left
Indoor-outdoor inter-unit wiring is cut or
is not connected correctly.
Same as at left
Reversed phase or open phase in the
3-phase power at one of the outdoor
units in the group
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Same as at left
Remote controller crossover wiring is cut or
is not connected correctly.
Indoor unit ceiling panel connector is not
connected correctly.
Remote controller crossover wiring is connected
to the indoor unit, however it is set for individual
operation.
Connect the remote controller correctly.
Turn ON the indoor unit power.
2 remote controllers are
set as the main remote
controller.
Check the remote controller and inter-unit
control wiring.
Perform automatic address setting.
Connect the remote controller correctly.
Refer to 11-8-6 Main-sub remote control, and
make the correct settings.
Check the remote controller crossover wiring.
Perform automatic address setting again.
Connect the wiring correctly.
Refer to 11-8 System Control, and make the
correct settings.
Check that the total capacities of the indoor
and outdoor units are appropriate.
Check that the indoor unit power is ON, and that
the inter-unit control wiring is connected correctly.
Reverse 2 phases of the outdoor unit 3-phase
power and connect them correctly.
Check that the indoor and outdoor unit types
are correct.
Perform automatic address setting.
Connect the indoor unit ceiling panel
connector correctly.
Ceiling panel connector at one of the
indoor units in the group is not
connected correctly.
Reversed phase or open phase in the
outdoor unit 3-phase power
1:1 connection (sing
o
r
G
)
e
p
y
t
e
l
up connection
Simultaneous-operation multi system
(flexible combination)
Control by main-sub
remote controllers
6-7. Table of Self-Diagnostic Functions and Corrections (X, T, U, K Type)